SFR Remodel - CEV100724-02716 Order to Vacate

Permit Reviews

Permit Number - TC-RES-0824-05045
Permit Status: Issued
Permit Description: SFR Remodel - CEV100724-02716 Order to Vacate
Start Date Submittal Complete Date Status  
09/13/2024 RESIDENTIAL NEW DWELLING v.2 10/16/2024 REQUIRES RESUBMIT Review Details
08/30/2024 RESIDENTIAL NEW DWELLING v.1 08/30/2024 REQUIRES RESUBMIT Review Details
11/08/2024 RESIDENTIAL NEW DWELLING v.3 12/03/2024 APPROVED Review Details

Conditions

Permit Number - TC-RES-0824-05045
Permit Status: Issued
Permit Description: SFR Remodel - CEV100724-02716 Order to Vacate
Date Description Comments
12/03/2024 Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/pdsd_owner_builder_affidavit_081623.pdf, is required prior to issuance of permit. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit.

Outstanding Inspections

Permit Status: Issued
Permit Number: TC-RES-0824-05045
Permite Description: SFR Remodel - CEV100724-02716 Order to Vacate
Total Outstanding Inspections - 6
Last Inspection Date Description Inspector Results Comments
10/25/2024 Building Inspection - Outside Normal Hours Building Inspection N/A Not Applicable (Used for Reference only)
12/10/2024 COT - RSPL - Gas Pressure Test N/A Not Ready
02/19/2025 RSBU - Building Final N/A Re-inspection required Step at back door is not correct. Step is too high., caulk in all toilets and sink, basins and countertops
2/19/25: seal penetration on roof where existing MAST was installed, gas piping support must be weather treated lumber, properly support EMT running out of main panel and seal 90 degree with weather approved cover, Exterior outlets on rear house are not GFI and need bubble covers, Condensate line cannot be run off of roof edge. It needs to be run down to the ground approximately 6 inches above with an elbow down, All hose bibs on exterior house require vacuum breakers, insulate all water lines and coat for UV protection.
02/19/2025 COT - RSEL - Electrical Final N/A Re-inspection required Exterior outlets on rear house are not GFI and need bubble covers
All hose bibs on exterior house require vacuum breakers
Please provide ladder for access to roof for inspection. Three runs required on an extension ladder above roof level and the ladder needs to be tied off. Condensate line cannot be run off of roof edge. It needs to be run down to the ground approximately 6 inches above with an elbow down.
Step at back door is not correct. Step is too high., caulk in all toilets and sink, basins and countertops
2/19/25: seal penetration on roof where existing MAST was installed, gas piping support must be weather treated lumber, properly support EMT running out of main panel and seal 90 degree with weather approved cover, Exterior outlets on rear house are not GFI and need bubble covers, Condensate line cannot be run off of roof edge. It needs to be run down to the ground approximately 6 inches above with an elbow down, All hose bibs on exterior house require vacuum breakers, insulate all water lines and coat for UV protection.
02/19/2025 COT - RSME - Mechanical Final N/A Re-inspection required Please provide ladder for access to roof for inspection. Three runs required on an extension ladder above roof level and the ladder needs to be tied off. Condensate line cannot be run off of roof edge. It needs to be run down to the ground approximately 6 inches above with an elbow down.
Step at back door is not correct. Step is too high., caulk in all toilets and sink, basins and countertops
2/19/25: seal penetration on roof where existing MAST was installed, gas piping support must be weather treated lumber, properly support EMT running out of main panel and seal 90 degree with weather approved cover, Exterior outlets on rear house are not GFI and need bubble covers, Condensate line cannot be run off of roof edge. It needs to be run down to the ground approximately 6 inches above with an elbow down, All hose bibs on exterior house require vacuum breakers, insulate all water lines and coat for UV protection.
02/19/2025 COT - RSPL - Plumbing Final N/A Re-inspection required All hose bibs on exterior house require vacuum breakers
Please provide ladder for access to roof for inspection. Three runs required on an extension ladder above roof level and the ladder needs to be tied off. Condensate line cannot be run off of roof edge. It needs to be run down to the ground approximately 6 inches above with an elbow down.
Step at back door is not correct. Step is too high., caulk in all toilets and sink, basins and countertops
2/19/25: seal penetration on roof where existing MAST was installed, gas piping support must be weather treated lumber, properly support EMT running out of main panel and seal 90 degree with weather approved cover, Exterior outlets on rear house are not GFI and need bubble covers, Condensate line cannot be run off of roof edge. It needs to be run down to the ground approximately 6 inches above with an elbow down, All hose bibs on exterior house require vacuum breakers, insulate all water lines and coat for UV protection.

Completed Inspections

Permit Status: Issued
Permit Number: TC-RES-0824-05045
Permit Description: SFR Remodel - CEV100724-02716 Order to Vacate