Permit Number: TC-RES-0824-05045
Parcel: 116161510

Address:
1027 N ANITA AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.2

Permit Number - TC-RES-0824-05045
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2024 Site Engineering NOT REQUIRED
10/04/2024 Site Landscape NOT REQUIRED
10/16/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/17/2024 Residential Building REQUIRES RESUBMIT TC-RES-0824-05045
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all progress inspections.

Provide a response letter on separate file with the updated construction plan set.

Provide a clear and concise construction plan set. Sample drawings are available for understanding details. Sample plans at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

SITE PLAN:

1. Identify the meaning of No. 1017 appearing on the existing house outline, R106.1.1.

PLANS:

1. Provide a complete floor plan showing the function of each room, R106.1.1.

PLUMBING PLANS:

1. Show the location of altered or repaired plumbing fixtures.
2. Show new or replaced gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1).

MECHANICAL PLANS:

1. Show the HVAC system size in accordance with building demand, M1401.3, M1601.1.
2. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Obtained from the installer.

ELECTRICAL PLANS:

1. Show a smoke alarm in each bedroom and outside the doorway in the immediate vicinity, R314.3.
2. Designate the circuit number at the location of each new or replaced light fixture, receptacle, appliance, and equipment disconnect switch, R106.1.1.
3. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2.
4. Provide a panel schedule showing wire size of each circuit or notate the wire size for each protection rating, E3702.2.
5. Interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights, and smoke detectors require combination type arc-fault circuit interrupters, E3902.16. Add notation to plans.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
10/16/2024 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Ramiro Olivarez
Planner, Zoning Review Section

PROJECT: TC-RES-0824-05045
1027 N ANITA AV TUCSON, AZ 85705 - R-3 Zoning
SFR Remodel (1st Review)

TRANSMITTAL DATE: 10/16/2024

This site is located in the R-3 zone (Unified Development Code (UDC) Article 4.7.12). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6.

1. Comment: While there are no comments for the internal remodel, Zoning will not approve this review until Residential Building has approved their review.
2. Comment: Clarify what the patio is on the southwestern portion of the existing house. Indicate if it is covered.
3. Comment: Additional comments may be forthcoming on the next review based on the proposed use for the addition and applicable use specific standards.

If you have any questions about this transmittal, please contact Ramiro Olivarez at Ramiro.Olivarez@tucsonaz.gov
09/13/2024 PDSD Application Completeness Express REVIEW COMPLETED