T15CM00101 FINALS ONLY-Solar panels are installed, I just need the permit to finish the job.
Permit Reviews
Permit Number - TC-RES-0824-05007
Permit Status: Complete
Permit Description: T15CM00101 FINALS ONLY-Solar panels are installed, I just need the permit to finish the job.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/08/2024 | RESIDENTIAL SOLAR v.2 | 10/08/2024 | REQUIRES RESUBMIT |
| 01/30/2025 | RESIDENTIAL SOLAR v.3 | 01/30/2025 | REQUIRES RESUBMIT |
| 08/28/2024 | RESIDENTIAL SOLAR v.1 | 08/28/2024 | REQUIRES RESUBMIT |
| 01/30/2025 | RESIDENTIAL SOLAR v.4 | 01/31/2025 | APPROVED |
Outstanding Inspections
Permit Status: Complete
Permit Number: TC-RES-0824-05007
Permite Description: T15CM00101 FINALS ONLY-Solar panels are installed, I just need the permit to finish the job.
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2025 | BULD - Electrical Clearance | N/A | Re-inspection required | 05/09/25 1. Bond bushings required throughout; 2. photovoltaic labels needed on conduit rooftop; 3. LABEL Needed at main service panel, DEPICTING A BUILDING WITH A ROOF THAT READS "SOLAR PV SYSTEM IS EQUIPPED WITH RAPID SHUTDOWN", AS WELL AS, "TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY" PER 2017 NEC 690.56(C)(1)(A) |
| 05/09/2025 | COT - RSOL - Electrical Final Solar Project | N/A | Re-inspection required | 05/09/25 1. Bond bushings required throughout; 2. photovoltaic labels needed on conduit rooftop; 3. LABEL Needed at main service panel, DEPICTING A BUILDING WITH A ROOF THAT READS "SOLAR PV SYSTEM IS EQUIPPED WITH RAPID SHUTDOWN", AS WELL AS, "TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY" PER 2017 NEC 690.56(C)(1)(A) |
| 05/09/2025 | RSBU - Building Final | N/A | Re-inspection required | 05/09/25 1. Bond bushings required throughout; 2. photovoltaic labels needed on conduit rooftop; 3. LABEL Needed at main service panel, DEPICTING A BUILDING WITH A ROOF THAT READS "SOLAR PV SYSTEM IS EQUIPPED WITH RAPID SHUTDOWN", AS WELL AS, "TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY" PER 2017 NEC 690.56(C)(1)(A) |
Completed Inspections
Permit Status: Complete
Permit Number: TC-RES-0824-05007
Permit Description: T15CM00101 FINALS ONLY-Solar panels are installed, I just need the permit to finish the job.
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/23/2025 | BULD - Electrical Clearance | Passed | Approved all items addressed, DGC Clearance to TEP is required (separate service panel upgrades is required) | |
| 06/23/2025 | COT - RSOL - Electrical Final Solar Project | Passed | Approved all items addressed, DGC Clearance to TEP is required (separate service panel upgrades is required) | |
| 06/23/2025 | RSBU - Building Final | Passed |