Permit Details

Status:
Complete
Type:
Residential Building - One or Two Family
Address NEW:
929 W PENNSYLVANIA ST
Apply Date:
08/27/2024
Applicant:
Luis Trujillo
Description:
T15CM00101 FINALS ONLY-Solar panels are installed, I just need the permit to finish the job.

Permit Reviews

Permit Number - TC-RES-0824-05007
Permit Status: Complete
Permit Description: T15CM00101 FINALS ONLY-Solar panels are installed, I just need the permit to finish the job.
Start Date Submittal Complete Date Status  
10/08/2024 RESIDENTIAL SOLAR v.2 10/08/2024 REQUIRES RESUBMIT Review Details
01/30/2025 RESIDENTIAL SOLAR v.3 01/30/2025 REQUIRES RESUBMIT Review Details
08/28/2024 RESIDENTIAL SOLAR v.1 08/28/2024 REQUIRES RESUBMIT Review Details
01/30/2025 RESIDENTIAL SOLAR v.4 01/31/2025 APPROVED Review Details

Outstanding Inspections

Permit Status: Complete
Permit Number: TC-RES-0824-05007
Permite Description: T15CM00101 FINALS ONLY-Solar panels are installed, I just need the permit to finish the job.
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
05/09/2025 BULD - Electrical Clearance N/A Re-inspection required 05/09/25
1. Bond bushings required throughout;
2. photovoltaic labels needed on conduit rooftop;
3. LABEL Needed at main service panel, DEPICTING A BUILDING WITH A ROOF THAT READS "SOLAR PV SYSTEM IS EQUIPPED WITH RAPID SHUTDOWN", AS WELL AS, "TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY" PER 2017 NEC 690.56(C)(1)(A)
05/09/2025 COT - RSOL - Electrical Final Solar Project N/A Re-inspection required 05/09/25
1. Bond bushings required throughout;
2. photovoltaic labels needed on conduit rooftop;
3. LABEL Needed at main service panel, DEPICTING A BUILDING WITH A ROOF THAT READS "SOLAR PV SYSTEM IS EQUIPPED WITH RAPID SHUTDOWN", AS WELL AS, "TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY" PER 2017 NEC 690.56(C)(1)(A)
05/09/2025 RSBU - Building Final N/A Re-inspection required 05/09/25
1. Bond bushings required throughout;
2. photovoltaic labels needed on conduit rooftop;
3. LABEL Needed at main service panel, DEPICTING A BUILDING WITH A ROOF THAT READS "SOLAR PV SYSTEM IS EQUIPPED WITH RAPID SHUTDOWN", AS WELL AS, "TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY" PER 2017 NEC 690.56(C)(1)(A)

Completed Inspections

Permit Status: Complete
Permit Number: TC-RES-0824-05007
Permit Description: T15CM00101 FINALS ONLY-Solar panels are installed, I just need the permit to finish the job.
Total Completed Inspections - 3
Date Description Inspector Results Comments
06/23/2025 BULD - Electrical Clearance Passed Approved all items addressed, DGC Clearance to TEP is required (separate service panel upgrades is required)
06/23/2025 COT - RSOL - Electrical Final Solar Project Passed Approved all items addressed, DGC Clearance to TEP is required (separate service panel upgrades is required)
06/23/2025 RSBU - Building Final Passed