Inspection History Details
Inspection Status: Re-inspection required
Inspection History: RSBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2025 | RSBU - Building Final | Re-inspection required | 4/25/25 Called and left voicemail, no answer. |
|
| 05/02/2025 | RSBU - Building Final | Re-inspection required | 05/02/2025 Missing plans. Please submit plans for review, and request clearance inspection after plans have been reviewed and stamped by the City. |
|
| 05/09/2025 | RSBU - Building Final | Re-inspection required | 05/09/25 1. Bond bushings required throughout; 2. photovoltaic labels needed on conduit rooftop; 3. LABEL Needed at main service panel, DEPICTING A BUILDING WITH A ROOF THAT READS "SOLAR PV SYSTEM IS EQUIPPED WITH RAPID SHUTDOWN", AS WELL AS, "TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY" PER 2017 NEC 690.56(C)(1)(A) |
|
| 06/23/2025 | RSBU - Building Final | Passed |