Permit Details

Status:
Inspections
Type:
Residential Building - One or Two Family
Address NEW:
3501 E WILLARD ST
Apply Date:
03/20/2024
Applicant:
Stuart Meeks
Description:
Fire Damage Repair and Upgrade

Permit Reviews

Permit Number - TC-RES-0324-01669
Permit Status: Inspections
Permit Description: Fire Damage Repair and Upgrade
Start Date Submittal Complete Date Status  
03/21/2024 RESIDENTIAL NEW DWELLING v.1 03/21/2024 REQUIRES RESUBMIT Review Details
06/06/2024 RESIDENTIAL NEW DWELLING v.2 07/03/2024 APPROVED Review Details
04/08/2024 RESIDENTIAL NEW DWELLING v.1 05/07/2024 REQUIRES RESUBMIT Review Details

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-RES-0324-01669
Permite Description: Fire Damage Repair and Upgrade
Total Outstanding Inspections - 5
Last Inspection Date Description Inspector Results Comments
08/15/2025 RSBU - Building Final N/A Re-inspection required 8.15.2025
Outdoor laundry room has receptacles with exposed wires, one receptacle is over-filled, and is using drywall screws to secure. Hot water heater PRV valve line needs to terminate between 24"-6" from grade, bathroom toilet doesn’t have 15” clearance from wall or 21" from the front to the shower, kitchen sink doesn’t have shutoff valves below, range oven is not secured from tilting. Roof AC needs paint for pvc condensate line, heat kit not specified, no flashing at roof jacks or electrical conduit.
08/15/2025 COT - RSEL - Electrical Final N/A Re-inspection required 8.15.2025
Outdoor laundry room has receptacles with exposed wires, one receptacle is over-filled, and is using drywall screws to secure. Hot water heater PRV valve line needs to terminate between 24"-6" from grade, bathroom toilet doesn’t have 15” clearance from wall or 21" from the front to the shower, kitchen sink doesn’t have shutoff valves below, range oven is not secured from tilting. Roof AC needs paint for pvc condensate line, heat kit not specified, no flashing at roof jacks or electrical conduit.
08/15/2025 COT - RSME - Mechanical Final N/A Re-inspection required 8.15.2025
Outdoor laundry room has receptacles with exposed wires, one receptacle is over-filled, and is using drywall screws to secure. Hot water heater PRV valve line needs to terminate between 24"-6" from grade, bathroom toilet doesn’t have 15” clearance from wall or 21" from the front to the shower, kitchen sink doesn’t have shutoff valves below, range oven is not secured from tilting. Roof AC needs paint for pvc condensate line, heat kit not specified, no flashing at roof jacks or electrical conduit.
08/15/2025 COT - RSPL - Plumbing Final N/A Re-inspection required 8.15.2025
Outdoor laundry room has receptacles with exposed wires, one receptacle is over-filled, and is using drywall screws to secure. Hot water heater PRV valve line needs to terminate between 24"-6" from grade, bathroom toilet doesn’t have 15” clearance from wall or 21" from the front to the shower, kitchen sink doesn’t have shutoff valves below, range oven is not secured from tilting. Roof AC needs paint for pvc condensate line, heat kit not specified, no flashing at roof jacks or electrical conduit.
08/15/2025 COT - RSEL - Outdoor Lighting N/A Re-inspection required 8.15.2025
Outdoor laundry room has receptacles with exposed wires, one receptacle is over-filled, and is using drywall screws to secure. Hot water heater PRV valve line needs to terminate between 24"-6" from grade, bathroom toilet doesn’t have 15” clearance from wall or 21" from the front to the shower, kitchen sink doesn’t have shutoff valves below, range oven is not secured from tilting. Roof AC needs paint for pvc condensate line, heat kit not specified, no flashing at roof jacks or electrical conduit.

Completed Inspections

Permit Status: Inspections
Permit Number: TC-RES-0324-01669
Permit Description: Fire Damage Repair and Upgrade
Total Completed Inspections - 5
Date Description Inspector Results Comments
07/19/2024 COT - RSBU - Roof Nailing Passed
02/27/2025 COT - RSPL - Gas Pressure Test Passed
03/19/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed
06/04/2025 BULD - Electrical Clearance Passed Approved for electrical reconnection - RECN Clearance to TEP is required
06/04/2025 COT - BULD - SWG Clearance Passed Approved pressure test for gas reconnection, SWG Clearance is required

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
COT - FPU - FLOODPLAIN USE_V1.PDF DOCUMENTS VIEW