Permit: TC-RES-0324-01669
Permit Details
Status:
Inspections
Type:
Residential Building - One or Two Family
Address:
3501 E WILLARD ST
Address NEW:
3501 E WILLARD ST
Apply Date:
03/20/2024
Applicant:
Stuart Meeks
Description:
Fire Damage Repair and Upgrade
Permit Reviews
Permit Number - TC-RES-0324-01669
Permit Status: Inspections
Permit Description: Fire Damage Repair and Upgrade
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/21/2024 | RESIDENTIAL NEW DWELLING v.1 | 03/21/2024 | REQUIRES RESUBMIT |
| 06/06/2024 | RESIDENTIAL NEW DWELLING v.2 | 07/03/2024 | APPROVED |
| 04/08/2024 | RESIDENTIAL NEW DWELLING v.1 | 05/07/2024 | REQUIRES RESUBMIT |
Outstanding Inspections
Permit Status: Inspections
Permit Number: TC-RES-0324-01669
Permite Description: Fire Damage Repair and Upgrade
Total Outstanding Inspections - 5
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/15/2025 | RSBU - Building Final | N/A | Re-inspection required | 8.15.2025 Outdoor laundry room has receptacles with exposed wires, one receptacle is over-filled, and is using drywall screws to secure. Hot water heater PRV valve line needs to terminate between 24"-6" from grade, bathroom toilet doesn’t have 15” clearance from wall or 21" from the front to the shower, kitchen sink doesn’t have shutoff valves below, range oven is not secured from tilting. Roof AC needs paint for pvc condensate line, heat kit not specified, no flashing at roof jacks or electrical conduit. |
| 08/15/2025 | COT - RSEL - Electrical Final | N/A | Re-inspection required | 8.15.2025 Outdoor laundry room has receptacles with exposed wires, one receptacle is over-filled, and is using drywall screws to secure. Hot water heater PRV valve line needs to terminate between 24"-6" from grade, bathroom toilet doesn’t have 15” clearance from wall or 21" from the front to the shower, kitchen sink doesn’t have shutoff valves below, range oven is not secured from tilting. Roof AC needs paint for pvc condensate line, heat kit not specified, no flashing at roof jacks or electrical conduit. |
| 08/15/2025 | COT - RSME - Mechanical Final | N/A | Re-inspection required | 8.15.2025 Outdoor laundry room has receptacles with exposed wires, one receptacle is over-filled, and is using drywall screws to secure. Hot water heater PRV valve line needs to terminate between 24"-6" from grade, bathroom toilet doesn’t have 15” clearance from wall or 21" from the front to the shower, kitchen sink doesn’t have shutoff valves below, range oven is not secured from tilting. Roof AC needs paint for pvc condensate line, heat kit not specified, no flashing at roof jacks or electrical conduit. |
| 08/15/2025 | COT - RSPL - Plumbing Final | N/A | Re-inspection required | 8.15.2025 Outdoor laundry room has receptacles with exposed wires, one receptacle is over-filled, and is using drywall screws to secure. Hot water heater PRV valve line needs to terminate between 24"-6" from grade, bathroom toilet doesn’t have 15” clearance from wall or 21" from the front to the shower, kitchen sink doesn’t have shutoff valves below, range oven is not secured from tilting. Roof AC needs paint for pvc condensate line, heat kit not specified, no flashing at roof jacks or electrical conduit. |
| 08/15/2025 | COT - RSEL - Outdoor Lighting | N/A | Re-inspection required | 8.15.2025 Outdoor laundry room has receptacles with exposed wires, one receptacle is over-filled, and is using drywall screws to secure. Hot water heater PRV valve line needs to terminate between 24"-6" from grade, bathroom toilet doesn’t have 15” clearance from wall or 21" from the front to the shower, kitchen sink doesn’t have shutoff valves below, range oven is not secured from tilting. Roof AC needs paint for pvc condensate line, heat kit not specified, no flashing at roof jacks or electrical conduit. |
Completed Inspections
Permit Status: Inspections
Permit Number: TC-RES-0324-01669
Permit Description: Fire Damage Repair and Upgrade
Total Completed Inspections - 5
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/19/2024 | COT - RSBU - Roof Nailing | Passed | ||
| 02/27/2025 | COT - RSPL - Gas Pressure Test | Passed | ||
| 03/19/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | ||
| 06/04/2025 | BULD - Electrical Clearance | Passed | Approved for electrical reconnection - RECN Clearance to TEP is required | |
| 06/04/2025 | COT - BULD - SWG Clearance | Passed | Approved pressure test for gas reconnection, SWG Clearance is required |