Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSPL - Plumbing Final
Permit Number - TC-RES-0324-01669
Inspection Description - COT - RSPL - Plumbing Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/15/2025 | COT - RSPL - Plumbing Final | Re-inspection required | 8.15.2025 Outdoor laundry room has receptacles with exposed wires, one receptacle is over-filled, and is using drywall screws to secure. Hot water heater PRV valve line needs to terminate between 24"-6" from grade, bathroom toilet doesn’t have 15” clearance from wall or 21" from the front to the shower, kitchen sink doesn’t have shutoff valves below, range oven is not secured from tilting. Roof AC needs paint for pvc condensate line, heat kit not specified, no flashing at roof jacks or electrical conduit. |