Permit: TC-RES-0224-00659
Permit Details
Status:
Complete
Type:
Residential Building - One or Two Family
Address:
3353 N FORGEUS AV
Address NEW:
3353 N FORGEUS AV
Apply Date:
02/05/2024
Applicant:
alex enoch
Description:
SFR Remodel and Bedroom Suite Addition
Permit Reviews
Permit Number - TC-RES-0224-00659
Permit Status: Complete
Permit Description: SFR Remodel and Bedroom Suite Addition
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/05/2024 | RESIDENTIAL NEW DWELLING v.2 | 04/25/2024 | REQUIRES RESUBMIT |
| 06/21/2024 | RESTAMP - RESIDENTIAL v.1 | 06/21/2024 | APPROVED |
| 01/31/2025 | RESIDENTIAL NEW DWELLING REVISION v.1 | 03/04/2025 | APPROVED |
| 06/21/2024 | RESIDENTIAL NEW DWELLING v.4 | 06/21/2024 | APPROVED |
| 08/16/2024 | RESIDENTIAL NEW DWELLING v.2 | 09/17/2024 | APPROVED |
| 10/18/2024 | RESIDENTIAL NEW DWELLING REVISION v.1 | 11/20/2024 | APPROVED |
| 02/06/2024 | RESIDENTIAL NEW DWELLING v.1 | 03/04/2024 | REQUIRES RESUBMIT |
| 08/15/2024 | RESIDENTIAL NEW DWELLING v.1 | 08/16/2024 | REQUIRES RESUBMIT |
| 03/19/2026 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 03/20/2026 | APPROVED |
| 05/30/2024 | RESIDENTIAL NEW DWELLING v.3 | 06/20/2024 | REQUIRES RESUBMIT |
| 03/25/2025 | RESIDENTIAL NEW DWELLING REVISION v.1 | 04/23/2025 | APPROVED |
| 09/19/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 09/23/2025 | APPROVED |
Conditions
Permit Number - TC-RES-0224-00659
Permit Status: Complete
Permit Description: SFR Remodel and Bedroom Suite Addition
| Date | Description | Comments |
|---|---|---|
| 04/21/2025 | Manual J report | |
| 02/14/2024 | Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building. |
Outstanding Inspections
Permit Status: Complete
Permit Number: TC-RES-0224-00659
Permite Description: SFR Remodel and Bedroom Suite Addition
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2025 | COT - RSEL - Electrical Underground | N/A | Not Applicable | |
| 04/15/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | N/A | Re-inspection required | 15 April 25 1. Pancake boxes overloaded, no more than 6 Cubic inches. 2. Interior outlets are on the same circuits as exterior. 3. Hall bath bidet outlet too close to bathtub, needs to be 36" away minimum. 4. Hallway bath is missing Lav outlet. |
| 09/22/2025 | COT - RSPL - Plumbing Final | N/A | Not Ready |
Completed Inspections
Permit Status: Complete
Permit Number: TC-RES-0224-00659
Permit Description: SFR Remodel and Bedroom Suite Addition
Total Completed Inspections - 15
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2024 | COT - RSPL - Rough Soil | Passed | ||
| 11/06/2024 | COT - RSBU - Excavation/Rebar/Zoning | Passed | ||
| 11/06/2024 | COT - RSBU - Preslab | Passed | ||
| 01/22/2025 | COT - RSEL - Grounding/Bonding | Passed | ||
| 01/22/2025 | BULD - Electrical Clearance | Passed | ||
| 02/19/2025 | COT - RSBU - Roof Nailing | Passed | ||
| 02/19/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | ||
| 04/15/2025 | COT - RSPL - Gas Pressure Test | Passed | ||
| 04/15/2025 | COT - RSPL - Yard Water Line | Passed | ||
| 09/22/2025 | COT - RSEL - Electrical Final | Passed | ||
| 09/22/2025 | COT - RSME - Mechanical Final | Passed | ||
| 09/22/2025 | COT - RSEL - Outdoor Lighting | Passed | ||
| 09/29/2025 | COT - BULD - SWG Clearance | Passed | 9.29.2025 Clearance to SW Gas. |
|
| 02/27/2026 | COT - RSPL - Plumbing Final | Passed | ||
| 03/09/2026 | RSBU - Building Final | Passed | 3.9.26 Corrections made, approved |