Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/15/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Re-inspection required | 15 April 25 1. Pancake boxes overloaded, no more than 6 Cubic inches. 2. Interior outlets are on the same circuits as exterior. 3. Hall bath bidet outlet too close to bathtub, needs to be 36" away minimum. 4. Hallway bath is missing Lav outlet. |
|
| 04/18/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | 18 April 25 Pass; homeowner is okay with the Exterior and Living rooms circuits connected. |
|
| 04/18/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Re-inspection required | Partial pass pending note 2 on previous inspection. 4/18/2025 |