Permit Details

Status:
Inspections
Type:
Model Building Permit
Address NEW:
9985 E LEBARON DR
Apply Date:
02/10/2026
Applicant:
Celina Rodriguez
Description:
Mirador Ridge Skies 2013 Plan (Model master plan TC-MDP-0825-00417)

Permit Reviews

Permit Number - TC-MDP-0925-00519
Permit Status: Inspections
Permit Description: Mirador Ridge Skies 2013 Plan (Model master plan TC-MDP-0825-00417)
Start Date Submittal Complete Date Status  
02/12/2026 SITE FROM MODEL PERMIT - SUBDIVISION v.1 02/20/2026 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-MDP-0925-00519
Permit Status: Inspections
Permit Description: Mirador Ridge Skies 2013 Plan (Model master plan TC-MDP-0825-00417)
Total Outstanding Activity Conditions - 5
Date Name
02/19/2026 SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED.
02/19/2026 SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED.
02/19/2026 SPECIAL INSPECTION FOR SITE PREPARATION IS REQUIRED.
09/02/2025 Submit the Air Leakage & Duct Tightness Test Report completed by an Approved Special Inspector prior to Final Inspections.
09/02/2025 SPECIAL INSPECTION FOR POST TENSION SLAB IS REQUIRED.

Conditions

Permit Number - TC-MDP-0925-00519
Permit Status: Inspections
Permit Description: Mirador Ridge Skies 2013 Plan (Model master plan TC-MDP-0825-00417)
Date Description Comments
09/02/2025 Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit is required prior to issuance of permit. The Affidavit form is available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit.
09/02/2025 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900.
09/02/2025 Sewer condition must be accepted and released by Pima County prior to issuance of a Temporary Certificate of Occupancy. For More Information visit https://www.pima.gov/1076/Sewer-Connection-Permits, To check your permit status https://permits.pima.gov/

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-MDP-0925-00519
Permite Description: Mirador Ridge Skies 2013 Plan (Model master plan TC-MDP-0825-00417)
Total Outstanding Inspections - 9
Last Inspection Date Description Inspector Results Comments
04/08/2026 COT - RSBU - Excavation/Rebar/Zoning N/A Re-inspection required 04/08/2026
Provide underground conduit to kitchen island per plan, wrap greywater DWV pipe on north wall running through footing for protection.
04/08/2026 COT - RSEL - Electrical Underground N/A Re-inspection required 04/08/2026
Provide underground conduit to kitchen island per plan, wrap greywater DWV pipe on north wall running through footing for protection.
04/08/2026 COT - RSBU - Preslab N/A Re-inspection required 04/08/2026
Provide underground conduit to kitchen island per plan, wrap greywater DWV pipe on north wall running through footing for protection.
07/15/2026 COT - RSEL - Electrical Final N/A Re-inspection required 7/15/26: clean out must be cut to grade and capped, knock out at main panel must be sealed, panel schedule must be legible (marker is fading away at multiple circuits at panel), (2) AFCI circuits at panel keep tripping, PRV must be properly terminated ( no more than 6" AFF), weep screed clearance from grade shall be no less the 4", post tension tag required at hose bib, refrigerant caps missing at hvac condenser, non-metallic piping required to be marked at panel, receptacles must be re-checked due to circuits being off (multiple receptacles dead throughout), light fixtures in master bathroom not properly functioning, garbage disposal switch must be properly mounted, receptacles in laundry room must be GFCI, dryer box must display duct run on label, accessible door in garage has non compliant threshold, remove paint off 20-minute fire rated door at garage, garage door shall be self latching, properly support b-vent off of truss 6" min for single wall pipe,
07/15/2026 COT - RSEL - Outdoor Lighting N/A Re-inspection required 7/15/26: clean out must be cut to grade and capped, knock out at main panel must be sealed, panel schedule must be legible (marker is fading away at multiple circuits at panel), (2) AFCI circuits at panel keep tripping, PRV must be properly terminated ( no more than 6" AFF), weep screed clearance from grade shall be no less the 4", post tension tag required at hose bib, refrigerant caps missing at hvac condenser, non-metallic piping required to be marked at panel, receptacles must be re-checked due to circuits being off (multiple receptacles dead throughout), light fixtures in master bathroom not properly functioning, garbage disposal switch must be properly mounted, receptacles in laundry room must be GFCI, dryer box must display duct run on label, accessible door in garage has non compliant threshold, remove paint off 20-minute fire rated door at garage, garage door shall be self latching, properly support b-vent off of truss 6" min for single wall pipe,
07/15/2026 COT - RSME - Mechanical Final N/A Re-inspection required 7/15/26: clean out must be cut to grade and capped, knock out at main panel must be sealed, panel schedule must be legible (marker is fading away at multiple circuits at panel), (2) AFCI circuits at panel keep tripping, PRV must be properly terminated ( no more than 6" AFF), weep screed clearance from grade shall be no less the 4", post tension tag required at hose bib, refrigerant caps missing at hvac condenser, non-metallic piping required to be marked at panel, receptacles must be re-checked due to circuits being off (multiple receptacles dead throughout), light fixtures in master bathroom not properly functioning, garbage disposal switch must be properly mounted, receptacles in laundry room must be GFCI, dryer box must display duct run on label, accessible door in garage has non compliant threshold, remove paint off 20-minute fire rated door at garage, garage door shall be self latching, properly support b-vent off of truss 6" min for single wall pipe,
07/15/2026 COT - RSPL - Plumbing Final N/A Re-inspection required 7/15/26: clean out must be cut to grade and capped, knock out at main panel must be sealed, panel schedule must be legible (marker is fading away at multiple circuits at panel), (2) AFCI circuits at panel keep tripping, PRV must be properly terminated ( no more than 6" AFF), weep screed clearance from grade shall be no less the 4", post tension tag required at hose bib, refrigerant caps missing at hvac condenser, non-metallic piping required to be marked at panel, receptacles must be re-checked due to circuits being off (multiple receptacles dead throughout), light fixtures in master bathroom not properly functioning, garbage disposal switch must be properly mounted, receptacles in laundry room must be GFCI, dryer box must display duct run on label, accessible door in garage has non compliant threshold, remove paint off 20-minute fire rated door at garage, garage door shall be self latching, properly support b-vent off of truss 6" min for single wall pipe,
07/15/2026 ENGR Engineering Final N/A Not Ready HCS clean out needs to be trimmed.
Outstanding conditions need to be satisfied prior to final:
-Air leakage and duct tightness
-Concrete installation
-Epoxy anchors
-Post tension slab
-Site preparation
07/15/2026 RSBU - Building Final N/A Re-inspection required 7/15/26: clean out must be cut to grade and capped, knock out at main panel must be sealed, panel schedule must be legible (marker is fading away at multiple circuits at panel), (2) AFCI circuits at panel keep tripping, PRV must be properly terminated ( no more than 6" AFF), weep screed clearance from grade shall be no less the 4", post tension tag required at hose bib, refrigerant caps missing at hvac condenser, non-metallic piping required to be marked at panel, receptacles must be re-checked due to circuits being off (multiple receptacles dead throughout), light fixtures in master bathroom not properly functioning, garbage disposal switch must be properly mounted, receptacles in laundry room must be GFCI, dryer box must display duct run on label, accessible door in garage has non compliant threshold, remove paint off 20-minute fire rated door at garage, garage door shall be self latching, properly support b-vent off of truss 6" min for single wall pipe,

Completed Inspections

Permit Status: Inspections
Permit Number: TC-MDP-0925-00519
Permit Description: Mirador Ridge Skies 2013 Plan (Model master plan TC-MDP-0825-00417)
Total Completed Inspections - 15
Date Description Inspector Results Comments
03/20/2026 COT - RSPL - Rough Soil Passed 03/20/2026
Holding under test. Ok to backfill, shading required.
03/23/2026 COT - RSPL - Yard Water Line Passed 3/23/26 CORRECTIONS MADE
04/08/2026 COT - RSBU - Excavation/Rebar/Zoning Passed 04/08/2026
Approved per plan, all corrections made. Okay to proceed.
04/08/2026 COT - RSEL - Electrical Underground Passed 04/08/2026
Approved per plan, all corrections made. Okay to proceed.
04/08/2026 COT - RSBU - Preslab Passed 04/08/2026
Approved per plan, all corrections made. Okay to proceed.
04/17/2026 COT - RSBU - Roof Nailing Passed
04/17/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed
05/07/2026 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed
05/07/2026 COT - RSPL - Gas Pressure Test Passed
05/07/2026 COT - RSEL - Grounding/Bonding Passed
05/19/2026 COT - RSBU - Interior Shear Bracing Passed
06/17/2026 BULD - Electrical Clearance Passed
06/17/2026 COT - RSPL - Sewer Passed
07/10/2026 COT - BULD - SWG Clearance Passed 7-10-2026 SWG Clearance approved.
07/15/2026 RSBU - Building Progress Passed

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD (SSRS).PDF DOCUMENTS VIEW
MIRADOR RIDGE - LOT 162 START_V1.PDF DOCUMENTS VIEW
MRS 162 SIC-2026-02-10_V1.PDF DOCUMENTS VIEW