Permit Details

Status:
Issued
Type:
Model Building Permit
Apply Date:
04/12/2024
Applicant:
Daria Hopkins
Description:
SFR MER1402190 T21-M0078

Permit Reviews

Permit Number - TC-MDP-0424-00435
Permit Status: Issued
Permit Description: SFR MER1402190 T21-M0078
Start Date Submittal Complete Date Status  
10/08/2024 BUILDING DEFERRED SUBMITTAL REVIEW v.1 10/08/2024 APPROVED Review Details
04/15/2024 SITE FROM MODEL PERMIT - PRODUCTION v.1 04/22/2024 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-MDP-0424-00435
Permit Status: Issued
Permit Description: SFR MER1402190 T21-M0078
Total Outstanding Activity Conditions - 4
Date Name
04/18/2024 SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED.
04/18/2024 SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED.
04/18/2024 SPECIAL INSPECTION FOR POST TENSION SLAB IS REQUIRED.
04/18/2024 Post-Tension Inspection Report is required.

Conditions

Permit Number - TC-MDP-0424-00435
Permit Status: Issued
Permit Description: SFR MER1402190 T21-M0078
Date Description Comments
04/18/2024 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment.
10/08/2024 Sewer condition must be accepted and released by Pima County prior to issuance of a Temporary Certificate of Occupancy. For More Information visit https://www.pima.gov/1076/Sewer-Connection-Permits, To check your permit status https://permits.pima.gov/
04/18/2024 Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building.

Outstanding Inspections

Permit Status: Issued
Permit Number: TC-MDP-0424-00435
Permite Description: SFR MER1402190 T21-M0078
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
10/17/2024 BULD - Electrical Clearance N/A Re-inspection required 10-17-24, properly secure riser together with missing knockout at main panel.
10/17/24: seal all penetrations through vapor barrier, outdoor light fixtures are exceeding box fill 6 Cubic inches allowed, properly secure lath at pop outs, Thermostat shall be no higher than 54” above finish floor, pex needs proper support on vertical runs, remove lath material in attic, ground all metal fixtures, NM wiring must be secured 12” from box/fixtures, receptacle spacing at master bedroom not per code. FHA plate required at Dryer vent exhaust.
10/17/2024 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. N/A Re-inspection required 10-17-24, properly secure riser together with missing knockout at main panel.
10/17/24: seal all penetrations through vapor barrier, outdoor light fixtures are exceeding box fill 6 Cubic inches allowed, properly secure lath at pop outs, Thermostat shall be no higher than 54” above finish floor, pex needs proper support on vertical runs, remove lath material in attic, ground all metal fixtures, NM wiring must be secured 12” from box/fixtures, receptacle spacing at master bedroom not per code. FHA plate required at Dryer vent exhaust.

Completed Inspections

Permit Status: Issued
Permit Number: TC-MDP-0424-00435
Permit Description: SFR MER1402190 T21-M0078
Total Completed Inspections - 13
Date Description Inspector Results Comments
08/21/2024 COT - RSPL - Rough Soil Passed
08/21/2024 COT - RSPL - Sewer Passed
08/21/2024 COT - RSPL - Yard Water Line Passed
08/29/2024 COT - RSBU - Excavation/Rebar/Zoning Passed
08/29/2024 COT - RSBU - Preslab Passed
08/29/2024 COT - RSEL - Electrical Underground Passed
09/18/2024 COT - RSBU - Roof Nailing Passed
09/18/2024 COT - RSBU - Exterior Clips/Sheathing Passed
10/17/2024 COT - RSEL - Grounding/Bonding Passed 10-17-24, approved.
10/17/2024 COT - RSPL - Gas Pressure Test Passed 10-17-24, gas pressure test inspected and approved.
10/18/2024 BULD - Electrical Clearance Passed 10/18/24: ECO Clearance issued
10/18/2024 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed 10/18/24: Items noted on last inspection have been corrected. Okay to proceed with installation of insulation and drywall.
11/08/2024 COT - RSBU - Interior Shear Bracing Passed Drywall is properly secured to studs per plan requirements for interior shear walls. Okay to proceed with tape, texture, and paint.

Documents

File Name Document Type  
149845 PT LOT 49 COMPLETE-2024-10-08_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
LOT 49 APPLICATION_V1.PDF DOCUMENTS VIEW
LOT 49 PLOT PLAN_V1.PDF DOCUMENTS VIEW
LOT 49 SPECIAL INSPECTION CERTIFICATE-2024-04-12_V1.PDF DOCUMENTS VIEW