Inspection Status: Re-inspection required

Inspection History: BULD - Electrical Clearance

Permit Number - TC-MDP-0424-00435

Inspection Description - BULD - Electrical Clearance

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
10/17/2024 BULD - Electrical Clearance Re-inspection required 10-17-24, properly secure riser together with missing knockout at main panel.
10/17/24: seal all penetrations through vapor barrier, outdoor light fixtures are exceeding box fill 6 Cubic inches allowed, properly secure lath at pop outs, Thermostat shall be no higher than 54” above finish floor, pex needs proper support on vertical runs, remove lath material in attic, ground all metal fixtures, NM wiring must be secured 12” from box/fixtures, receptacle spacing at master bedroom not per code. FHA plate required at Dryer vent exhaust.
10/18/2024 BULD - Electrical Clearance Passed 10/18/24: ECO Clearance issued