Inspection History Details
Inspection Status: Re-inspection required
Inspection History: BULD - Electrical Clearance
Permit Number - TC-MDP-0424-00435
Inspection Description - BULD - Electrical Clearance
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/17/2024 | BULD - Electrical Clearance | Re-inspection required | 10-17-24, properly secure riser together with missing knockout at main panel. 10/17/24: seal all penetrations through vapor barrier, outdoor light fixtures are exceeding box fill 6 Cubic inches allowed, properly secure lath at pop outs, Thermostat shall be no higher than 54” above finish floor, pex needs proper support on vertical runs, remove lath material in attic, ground all metal fixtures, NM wiring must be secured 12” from box/fixtures, receptacle spacing at master bedroom not per code. FHA plate required at Dryer vent exhaust. |
|
10/18/2024 | BULD - Electrical Clearance | Passed | 10/18/24: ECO Clearance issued |