Permit Details

Status:
Inspections Complete
Type:
Model Building Permit
Address NEW:
6129 E FALCONRY TR
Apply Date:
02/20/2025
Applicant:
Alonzo Martinez
Description:
Blackhawk H30M Model Plan (Model Master Plan TC-MDP-0823-01436)

Permit Reviews

Permit Number - TC-MDP-0325-00161
Permit Status: Inspections complete
Permit Description: Blackhawk H30M Model Plan (Model Master Plan TC-MDP-0823-01436)
Start Date Submittal Complete Date Status  
03/06/2025 SITE FROM MODEL PERMIT - SUBDIVISION v.1 03/19/2025 APPROVED Review Details
06/25/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.1 06/25/2025 REQUIRES RESUBMIT Review Details
06/25/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.2 06/25/2025 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-MDP-0325-00161
Permit Status: Inspections complete
Permit Description: Blackhawk H30M Model Plan (Model Master Plan TC-MDP-0823-01436)
Total Outstanding Activity Conditions - 1
Date Name
03/04/2025 Sewer condition must be accepted and released by Pima County prior to issuance of a Temporary Certificate of Occupancy. For More Information visit https://www.pima.gov/1076/Sewer-Connection-Permits, To check your permit status https://permits.pima.gov/

Conditions

Permit Number - TC-MDP-0325-00161
Permit Status: Inspections complete
Permit Description: Blackhawk H30M Model Plan (Model Master Plan TC-MDP-0823-01436)
Date Description Comments
03/04/2025 Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/pdsd_owner_builder_affidavit_081623.pdf, is required prior to issuance of permit. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit.
03/04/2025 Post-Tension Inspection Report is required.
03/04/2025 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900.

Outstanding Inspections

Permit Status: Inspections Complete
Permit Number: TC-MDP-0325-00161
Permite Description: Blackhawk H30M Model Plan (Model Master Plan TC-MDP-0823-01436)
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
06/13/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. N/A Re-inspection required (with fee) 6-13-25: seal penetration of t-ply on second floor throughout . Areas marked in red.
06/23/2025 COT - RSBU - Interior Shear Bracing N/A Not Ready

Completed Inspections

Permit Status: Inspections Complete
Permit Number: TC-MDP-0325-00161
Permit Description: Blackhawk H30M Model Plan (Model Master Plan TC-MDP-0823-01436)
Total Completed Inspections - 21
Date Description Inspector Results Comments
05/05/2025 BULD - Electrical Clearance Passed 5/5/24: TEP ECO
05/07/2025 COT - RSPL - Yard Water Line Passed 5/5/25: Plumbing not per approved plans, Remove all debris from trench, backfill material shall be present on site at time of inspection.

P2503.5.1 Rough plumbing 1. Water test. Each section shall be filled with water to a point not less than 5 feet (1524 mm) above the highest fitting connection in that section, or to the highest point in the completed system. Water shall be held in the section under test for a period of 15 minutes. The system shall prove leak free by visual inspection.

P2604.1 Trenching and bedding.
Where trenches are excavated such that the bottom of the trench forms the bed for the pipe, solid and continuous load-bearing support shall be provided between joints. Where over-excavated, the trench shall be backfilled to the proper grade with compacted earth, sand, fine gravel or similar granular material. Piping shall not be supported on rocks or blocks at any point. Rocky or unstable soil shall be over-excavated by two or more pipe diameters and brought to the proper grade with suitable compacted granular material.

P2604.3 Backfilling.
Backfill shall be free from discarded construction material and debris. Backfill shall be free from rocks, broken concrete and frozen chunks until the pipe is covered by not less than 12 inches (305 mm) of tamped earth. Backfill shall be placed evenly on both sides of the pipe and tamped to retain proper alignment. Loose earth shall be carefully placed in the trench in 6-inch (152 mm) layers and tamped in place.
5/7/25: APPROVED OK TO PROCEED. SHADING REQUIRED
05/07/2025 COT - RSPL - Rough Soil Passed 5/5/25: Plumbing not per approved plans, Remove all debris from trench, backfill material shall be present on site at time of inspection.

P2503.5.1 Rough plumbing 1. Water test. Each section shall be filled with water to a point not less than 5 feet (1524 mm) above the highest fitting connection in that section, or to the highest point in the completed system. Water shall be held in the section under test for a period of 15 minutes. The system shall prove leak free by visual inspection.

P2604.1 Trenching and bedding.
Where trenches are excavated such that the bottom of the trench forms the bed for the pipe, solid and continuous load-bearing support shall be provided between joints. Where over-excavated, the trench shall be backfilled to the proper grade with compacted earth, sand, fine gravel or similar granular material. Piping shall not be supported on rocks or blocks at any point. Rocky or unstable soil shall be over-excavated by two or more pipe diameters and brought to the proper grade with suitable compacted granular material.

P2604.3 Backfilling.
Backfill shall be free from discarded construction material and debris. Backfill shall be free from rocks, broken concrete and frozen chunks until the pipe is covered by not less than 12 inches (305 mm) of tamped earth. Backfill shall be placed evenly on both sides of the pipe and tamped to retain proper alignment. Loose earth shall be carefully placed in the trench in 6-inch (152 mm) layers and tamped in place.
5/7/25: APPROVED OK TO PROCEED. SHADING REQUIRED
05/07/2025 COT - RSPL - Sewer Passed 5/5/25: Plumbing not per approved plans, Remove all debris from trench, backfill material shall be present on site at time of inspection.

P2503.5.1 Rough plumbing 1. Water test. Each section shall be filled with water to a point not less than 5 feet (1524 mm) above the highest fitting connection in that section, or to the highest point in the completed system. Water shall be held in the section under test for a period of 15 minutes. The system shall prove leak free by visual inspection.

P2604.1 Trenching and bedding.
Where trenches are excavated such that the bottom of the trench forms the bed for the pipe, solid and continuous load-bearing support shall be provided between joints. Where over-excavated, the trench shall be backfilled to the proper grade with compacted earth, sand, fine gravel or similar granular material. Piping shall not be supported on rocks or blocks at any point. Rocky or unstable soil shall be over-excavated by two or more pipe diameters and brought to the proper grade with suitable compacted granular material.

P2604.3 Backfilling.
Backfill shall be free from discarded construction material and debris. Backfill shall be free from rocks, broken concrete and frozen chunks until the pipe is covered by not less than 12 inches (305 mm) of tamped earth. Backfill shall be placed evenly on both sides of the pipe and tamped to retain proper alignment. Loose earth shall be carefully placed in the trench in 6-inch (152 mm) layers and tamped in place.
5/7/25: APPROVED OK TO PROCEED. SHADING REQUIRED
05/07/2025 COT - RSEL - Electrical Underground Passed
05/16/2025 COT - RSBU - Excavation/Rebar/Zoning Passed
05/16/2025 COT - RSEL - Grounding/Bonding Passed
05/16/2025 COT - RSBU - Preslab Passed
06/04/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 6-4-25: exterior clips/sheathing approved.
06/06/2025 COT - RSPL - Gas Pressure Test Passed 6-6-25: approved
06/13/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed
06/23/2025 COT - RSBU - Roof Nailing Passed 6/23/2026. Letter has been submitted to the Department on roof nailing inspection. Taking the full responsibility of the nailing pattern.
06/25/2025 COT - RSBU - Interior Shear Bracing Passed
08/13/2025 COT - RSEL - Electrical Final Passed
08/13/2025 COT - RSEL - Outdoor Lighting Passed
08/13/2025 COT - RSME - Mechanical Final Passed
08/13/2025 COT - RSPL - Plumbing Final Passed
08/13/2025 RSBU - Building Final Passed
08/13/2025 RSBU - Building Progress Passed
08/22/2025 COT - BULD - SWG Clearance Passed 8.8.25
SWG clearance approved
8/22/25: SWG clearance approved by Anthony Caballero
09/24/2025 ENGR Engineering Final Passed Site is complete in accordance with approved plans.

Documents

File Name Document Type  
BHK 135 SIC-2025-06-25_V2.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
BHK 135 D1_V1.PDF DOCUMENTS VIEW
BHK 135 SIC-2025-03-05_V1.PDF DOCUMENTS VIEW