Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Inspections
Type:
Commercial Building
Address NEW:
4945 S LIBERTY AV
Apply Date:
12/18/2024
Applicant:
Jeff Christopherson
Description:
The scope of work involves the renovation of an existing 96 unit senior community apartment complex.

Permit Reviews

Permit Number - TC-COM-1224-02366
Permit Status: Inspections
Permit Description: The scope of work involves the renovation of an existing 96 unit senior community apartment complex.
Start Date Submittal Complete Date Status  
12/23/2024 COMMERCIAL REVIEW - FULL v.1 01/15/2025 REQUIRES RESUBMIT Review Details
05/29/2025 COMMERCIAL REVIEW - FULL v.2 06/04/2025 REQUIRES RESUBMIT Review Details
06/24/2025 RESTAMP - COMMERCIAL v.1 06/25/2025 APPROVED Review Details
06/11/2025 COMMERCIAL REVIEW - FULL v.3 06/11/2025 REQUIRES RESUBMIT Review Details
10/01/2025 COMMERCIAL REVIEW - FULL REVISION v.2 10/07/2025 APPROVED Review Details
06/12/2025 COMMERCIAL REVIEW - FULL v.4 06/24/2025 APPROVED Review Details
10/01/2025 COMMERCIAL REVIEW - FULL REVISION v.1 10/01/2025 REQUIRES RESUBMIT Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-1224-02366
Permit Status: Inspections
Permit Description: The scope of work involves the renovation of an existing 96 unit senior community apartment complex.
Total Outstanding Activity Conditions - 2
Date Name
06/24/2025 AIR BALANCING REPORT IS REQUIRED.
06/24/2025 WATER STERILIZATION REPORT IS REQUIRED.

Conditions

Permit Number - TC-COM-1224-02366
Permit Status: Inspections
Permit Description: The scope of work involves the renovation of an existing 96 unit senior community apartment complex.
Date Description Comments
12/23/2024 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.
12/23/2024 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900.

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-COM-1224-02366
Permite Description: The scope of work involves the renovation of an existing 96 unit senior community apartment complex.
Total Outstanding Inspections - 6
Last Inspection Date Description Inspector Results Comments
02/20/2026 COT - HCBU - Building Final N/A Re-inspection required 2-20-26: called point of contact at 830am -no answer and unable to leave voice mail because it was full. Made contact with management at the office who said contractor was not on site and would be arriving sometime later. Please reschedule inspection at your convenience.
02/27/2026 COT - HCEL - Electrical Intermediate N/A Re-inspection required 2-27-26: precon meeting & a general walk through of MEP's at Unit B101. Fire foam all penetrations at top plates, add supports to in wall DWV under test/Domestic lines at shower, install shower backing as required per City of Tucson Inclusive requirements, add plumbers tape to DWV above ceiling that is resting on 2x4, and have engineer or architect of record submit a letter showing slight relocation of electrical panel to adjacent wall at living room and note that existing panel will be utilized as a junction box.
PDSD Building Division Pre-Construction Meeting N/A Scheduled
02/27/2026 COT - HCME - Mechanical Intermediate N/A Re-inspection required 2-27-26: precon meeting & a general walk through of MEP's at Unit B101. Fire foam all penetrations at top plates, add supports to in wall DWV under test/Domestic lines at shower, install shower backing as required per City of Tucson Inclusive requirements, add plumbers tape to DWV above ceiling that is resting on 2x4, and have engineer or architect of record submit a letter showing slight relocation of electrical panel to adjacent wall at living room and note that existing panel will be utilized as a junction box.
02/27/2026 COT - HCPL - Plumbing Intermediate N/A Re-inspection required 2-27-26: precon meeting & a general walk through of MEP's at Unit B101. Fire foam all penetrations at top plates, add supports to in wall DWV under test/Domestic lines at shower, install shower backing as required per City of Tucson Inclusive requirements, add plumbers tape to DWV above ceiling that is resting on 2x4, and have engineer or architect of record submit a letter showing slight relocation of electrical panel to adjacent wall at living room and note that existing panel will be utilized as a junction box.
COT - HCBU - Interior Shear Bracing N/A Scheduled

Scheduled Inspections

Scheduled Inspections - TC-COM-1224-02366
Status: Inspections
Description: The scope of work involves the renovation of an existing 96 unit senior community apartment complex.
Scheduled Date Description Entered By Entered Date
03/05/2026 COT - HCBU - Interior Shear Bracing Scheduled
03/05/2026 COT - HCME - Mechanical Intermediate Scheduled
03/05/2026 COT - HCPL - Plumbing Intermediate Scheduled
03/05/2026 PDSD Building Division Pre-Construction Meeting Scheduled
03/05/2026 COT - HCEL - Electrical Intermediate Scheduled
For information about today’s scheduled inspections please refer to the PDSD Daily Inspections Dashboards (Desktop) PDSD Daily Inspections Dashboards (Mobile) .

Documents

File Name Document Type  
TC-COM-1224-02366 - PERMIT CARD - REV VAL.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-P1.1-P2.1 - REVISED PLUMBING PLANS_V2.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW