Permit: TC-COM-1124-02264
Permit Details
Status:
Issued
Type:
Commercial Building
Address:
5205 E VALENCIA RD
Address NEW:
5205 E VALENCIA RD
Apply Date:
11/26/2024
Applicant:
Dave Damitio
Description:
McDonald's
Permit Reviews
Permit Number - TC-COM-1124-02264
Permit Status: Issued
Permit Description: McDonald's
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 06/17/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 06/18/2025 | APPROVED |
| 05/06/2025 | RESTAMP - COMMERCIAL v.1 | 05/08/2025 | APPROVED |
| 02/07/2025 | COMMERCIAL REVIEW - FULL v.2 | 03/13/2025 | REQUIRES RESUBMIT |
| 07/24/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 07/28/2025 | APPROVED |
| 04/03/2025 | COMMERCIAL REVIEW - FULL v.3 | 04/18/2025 | REQUIRES RESUBMIT |
| 12/05/2024 | COMMERCIAL REVIEW - FULL v.1 | 01/02/2025 | REQUIRES RESUBMIT |
| 04/23/2025 | COMMERCIAL REVIEW - FULL v.4 | 04/28/2025 | APPROVED |
| 04/28/2025 | RESTAMP - COMMERCIAL v.1 | 04/30/2025 | APPROVED |
Outstanding Activity Conditions
Permit Number - TC-COM-1124-02264
Permit Status: Issued
Permit Description: McDonald's
Total Outstanding Activity Conditions - 3
| Date | Name |
|---|---|
| 02/11/2025 | SPECIAL INSPECTION FOR FIELD WELDING IS REQUIRED. |
| 02/11/2025 | SPECIAL INSPECTION FOR FOUNDATION/EXCAVATION IS REQUIRED. |
| 05/14/2025 | SPECIAL INSPECTION FOR OUTDOOR LIGHTING IS REQUIRED. |
Conditions
Permit Number - TC-COM-1124-02264
Permit Status: Issued
Permit Description: McDonald's
| Date | Description | Comments |
|---|---|---|
| 12/05/2024 | Permit address has been updated based on information provided P25AD00159 | |
| 12/05/2024 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. | |
| 12/05/2024 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. | |
| 02/11/2025 | A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. |
Outstanding Inspections
Permit Status: Issued
Permit Number: TC-COM-1124-02264
Permite Description: McDonald's
Total Outstanding Inspections - 12
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| COT - FCON - Sprinkler - Final | N/A | Not Ready | This was an inspection of the sweep for the riser. It extended about 8-10 feet from the building. | |
| 08/12/2025 | COT - HCPL - Plumbing Intermediate | N/A | Re-inspection required | 8-12-25: firefoam penetrations at top plates and firefoam any penetrations from an unconditioned space to a conditioned space, add straps to pex at north wall and 4x8" boca plates to DWV. Note: some areas were marked but not all.Walk site and add Boca plates where required. Also, where DWV runs through plates and have been notched more than 60% then FHA plates are required. That space in between must be firefomed too. This includes electrical as well. |
| COT - FCON - Hood System - Final | N/A | Not Ready | ||
| 06/09/2025 | COT - HCBU - Excavation/Rebar/Zoning | N/A | Partial Pass | 6-9-25: reinforcement at stem wall verified per plans. Okay to pour at progress areas. |
| 07/24/2025 | COT - HCEL - Electrical Underground | N/A | Canceled | 7-24-25: inspection must be made by engineering. |
| 08/12/2025 | COT - HCEL - Electrical Intermediate | N/A | Re-inspection required | 8-12-25: add firefoam to penetrations at top plates and FHA plates where blocking and or top plates where notched to run conduits. Note; some areas were marked but not all. Walk job site and add plates where required. |
| 09/18/2025 | COT - HCEL - Electrical Above Ceiling | N/A | Partial Pass | 9-18-25: over 95% of junction boxes labeled, all wiring/conduits verified in place. Pending bonding/grounding, some kitchen light-work at chases. Okay to install ceiling tiles at progress areas. |
| 08/12/2025 | COT - HCPL - Plumbing Above Ceiling | N/A | Partial Pass | 8-12-25: plumbing above ceiling supports verified per plans.Dampers, registers, hood system and refrigerant lines not yet installed. |
| 08/12/2025 | COT - HCME - Mechanical Intermediate | N/A | Partial Pass | 8-12-25: remove all flex from grid and support per plans/code. Dampers, registers, hood system and refrigerant lines not yet installed. |
| 08/06/2025 | COT - HCPL - Plumbing Progress | N/A | Partial Pass | Partial pass. New 2" service water line in place from meter location to building. Air pressure was inspected. Okay to backfill progress areas. Shading is required. 8/6/2025 |
| 09/18/2025 | COT - HCEL - Grounding/Bonding | N/A | Not Ready | 9-18-25: grounding/bonding not ready. |
| 12/03/2025 | COT - HCEL - Electrical Final | N/A | Partial Pass | 12-3-25: electrical final approved. Note: partial pass pending 3rd party inspection for outdoor lighting. |
Completed Inspections
Permit Status: Issued
Permit Number: TC-COM-1124-02264
Permit Description: McDonald's
Total Completed Inspections - 25
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2025 | COT - HCPL - Rough Soil | Passed | ||
| 07/02/2025 | COT - HCBU - Preslab | Passed | Reinforcements per plan. Okay for concrete placement in pad. 7/2/2025 | |
| 07/18/2025 | COT - HCBU - Roof Nailing | Passed | 7-18-25: nailing at rooftop decking, parapet nailing, and clips verified per plans. Okay to dry-in progress areas. | |
| 07/23/2025 | COT - HCBU - Framing | Passed | 7-23-25: verified HTT4's, anchor bolts/hangers/ kickers,bracing together with all interior framing/metal framing. Okay to continue with construction at progress areas. | |
| 07/23/2025 | COT - HCBU - Exterior Clips/Sheathing | Passed | 7-23-25: exterior clips/sheathing approved. Okay to continue with construction at progress areas | |
| 08/12/2025 | COT - HCPL - Gas Pressure Test | Passed | 8-12-25: gas pressure test approved. | |
| 08/12/2025 | COT - HCPL - Plumbing Roof Drains | Passed | 8-12-25: floor drain per plans and verified under test. | |
| 10/27/2025 | COT - HCBU - Building Progress | Passed | ||
| 10/27/2025 | COT - HCBU - Masonry Pregrout | Passed | ||
| 10/27/2025 | HCBU - Preslab and Floodplain Inspection | Passed | ||
| 10/27/2025 | COT - HCBU - Excavation/Rebar/Zoning | Passed | ||
| 10/27/2025 | COT - HCEL - Electrical Underground | Passed | ||
| 10/27/2025 | COT - HCEL - Electrical Intermediate | Passed | ||
| 10/27/2025 | COT - HCME - Kitchen Hood | Passed | ||
| 11/04/2025 | COT - BULD - SWG Clearance | Passed | 11-4-25: okay to install meter-SWG clearance issued. | |
| 11/17/2025 | BULD - Electrical Clearance | Passed | 11-17-25: okay to energize SES. ECO clearance issued to TEP. | |
| 11/18/2025 | COT - HCBU - Building Above Ceiling | Passed | ||
| 11/18/2025 | COT - HCEL - Electrical Above Ceiling | Passed | ||
| 11/18/2025 | COT - HCME - Mechanical Above Ceiling | Passed | ||
| 11/18/2025 | COT - HCPL - Plumbing Above Ceiling | Passed | ||
| 11/18/2025 | COT - HCEL - Electrical Progress | Passed | ||
| 11/18/2025 | COT - HCME - Mechanical Intermediate | Passed | ||
| 11/18/2025 | COT - HCME - Mechanical Progress | Passed | ||
| 11/18/2025 | COT - HCPL - Plumbing Progress | Passed | ||
| 11/18/2025 | COT - HCEL - Grounding/Bonding | Passed |