Inspection Status: Re-inspection required

Inspection History: COT - HCPL - Plumbing Intermediate 

Permit Number - TC-COM-1124-02264

Inspection Description - COT - HCPL - Plumbing Intermediate 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
08/12/2025 COT - HCPL - Plumbing Intermediate  Re-inspection required 8-12-25: firefoam penetrations at top plates and firefoam any penetrations from an unconditioned space to a conditioned space, add straps to pex at north wall and 4x8" boca plates to DWV. Note: some areas were marked but not all.Walk site and add Boca plates where required. Also, where DWV runs through plates and have been notched more than 60% then FHA plates are required. That space in between must be firefomed too. This includes electrical as well.
08/13/2025 COT - HCPL - Plumbing Intermediate  Re-inspection required 8-13-25: firefoam penetrations throughout.
08/14/2025 COT - HCPL - Plumbing Intermediate  Partial Pass 8-14-25: add Boca plates at top plates to protect DWV. Boca plates to be verified prior to installation of interior wall finish. Okay to continue with construction at progress areas.