Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Inspections
Type:
Commercial Building
Address:
3301 E GLOBAL LP
Address NEW:
3301 E GLOBAL LP
Apply Date:
09/12/2024
Applicant:
James Lynch
Description:
Removal of existing parking spaces and addition of new concrete slab and fence with new exterior genrator. update to existing SES. No change to the existing occupancy or area of the existing building.

Permit Reviews

Permit Number - TC-COM-0924-01780
Permit Status: Inspections
Permit Description: Removal of existing parking spaces and addition of new concrete slab and fence with new exterior genrator. update to existing SES. No change to the existing occupancy or area of the existing building.
Start Date Submittal Complete Date Status  
12/19/2024 COMMERCIAL REVIEW - FULL REVISION v.1 01/14/2025 APPROVED Review Details
09/16/2024 COMMERCIAL REVIEW - FULL v.1 10/16/2024 REQUIRES RESUBMIT Review Details
10/29/2024 RESTAMP - COMMERCIAL v.1 11/01/2024 APPROVED Review Details
10/23/2024 COMMERCIAL REVIEW - FULL v.2 10/29/2024 APPROVED Review Details

Conditions

Permit Number - TC-COM-0924-01780
Permit Status: Inspections
Permit Description: Removal of existing parking spaces and addition of new concrete slab and fence with new exterior genrator. update to existing SES. No change to the existing occupancy or area of the existing building.
Date Description Comments
09/16/2024 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-COM-0924-01780
Permite Description: Removal of existing parking spaces and addition of new concrete slab and fence with new exterior genrator. update to existing SES. No change to the existing occupancy or area of the existing building.
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
06/09/2025 COT - HCBU - Preslab N/A Partial Pass Pad for new CT can location per detail 103/S1.0 approved. Okay for concrete placement. 6/9/2025
06/09/2025 COT - HCBU - Excavation/Rebar/Zoning N/A Partial Pass Pad for new CT can location per detail 103/S1.0 approved. Okay for concrete placement. 6/9/2025

Completed Inspections

Permit Status: Inspections
Permit Number: TC-COM-0924-01780
Permit Description: Removal of existing parking spaces and addition of new concrete slab and fence with new exterior genrator. update to existing SES. No change to the existing occupancy or area of the existing building.
Total Completed Inspections - 9
Date Description Inspector Results Comments
05/08/2025 COT - HCPL - Gas Pressure Test Passed 5-8-25, approximately 160' of 4" Schedule 40 conduit with tracer wire verified under test. Okay to backfill with shading materials.
05/12/2025 COT - HCEL - Grounding/Bonding Passed Approved Grounding Ring 4/0 Cu with 6 Rods, okay to backfill progress areas
02/18/2026 COT - HCEL - Electrical Progress Passed 2-18-26: approved.
02/18/2026 COT - HCBU - Preslab Passed 2-18-26: previously inspected & approved.
02/18/2026 COT - HCBU - Excavation/Rebar/Zoning Passed 2-18-26: previously inspected & approved.
02/18/2026 COT - HCEL - Electrical Underground Passed 2-18-26: approved.
04/11/2026 Building Inspection - Outside Normal Hours Building Inspection Passed 4-11-26: new Nema, 3R, 1000A-277/480V SES together with new natural generator installed per approved plans. Verbal INCR clearance to energize system given at 1416 hours.
04/11/2026 BULD - Electrical Clearance Passed 4-11-26: new Nema, 3R, 1000A-277/480V SES together with new natural generator installed per approved plans. Verbal INCR clearance to energize system given at 1416 hours.
06/04/2026 COT - HCEL - Electrical Final Passed 6-4-26: electrical final approved.

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-REV1_BUILDING SET_V1.PDF DOCUMENTS VIEW
REVISION_1 NARRATIVE_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-BUILDING SET 9 9 24_V2.PDF DOCUMENTS VIEW