Permit Number: TC-COM-0924-01780
Parcel: 140290290

Address:
3301 E GLOBAL LP

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0924-01780
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2024 Site Engineering APPROVED
10/16/2024 Site Zoning APPROVED
10/16/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/01/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 9/28/2024 6:54:29 PM




Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 9/17/2024 7:53:51 AM
1. Sheet S1.0 – Sheet S1.1 typical fence section detail limits fence foundations at 8’-0” max spacing but new electrical foundation plan shows spacing over 8 feet at 10’-6”. S1.1 does not provide typical double gate detail: only single gate
provided.
2. Sheet A000 – Project location note to see details 1 and 2 on sheet DP5 but this sheet is not provided.
3. Sheet A001 – note 32.07 showing new steel fence at 7’-0” but sheet S1.1 specifies 8 feet high fence.
4. Demolition plan missing. Clearly indicate the demolition scope of work such ten existing parking spaces to be removed. Identify if any accessible / ADA parking spaces are being removed or any remaining.
5. Sheet E100 – Note 14 new natural gas generator does not mention how gas is provided. 2018 International Fuel Gas Code section 402.1 piping system shall be of such size and so installed as to provide a supply of gas sufficient to meet
the maximum demand and supply gas to each appliance inlet no less than the minimum supply pressure required by the appliance.
6. Sheet S1.0 – Show the pad dimensions. Size and area of pad width and length dimensions are missing for construction.






Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 9/30/2024 10:17:00 AM
1. General - Provide under either Mechanical or Plumbing the (underground and or the above ground) routing, size, valves, dirt legs and any other equipment or device attached to or part of the Natural Gas lines. - 2018 IECC Section C103.2Information on construction documents. - 2018 IBC – Section [A]107.2.1Information on construction documents.
2. General - Provide an Isometric drawing of the same request as per Comment #1. - Provide under either Mechanical or Plumbing the (underground and or the above ground) routing, size, valves, dirt legs and any other equipment or device
attached to or part of the Natural Gas lines. - 2018 IECC Section C103.2Information on construction documents. -
2018 IBC – Section [A]107.2.1Information on construction documents.





Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 9/17/2024 4:04:08 PM






Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 9/30/2024 8:51:39 PM
FIRST GAS REVIEW:
1). GENERAL: MISSING GAS PLANS. PROVIDE COMPLETE PLAN THAT INCLUDE GAS PIPING ILLUSTRATIONS, GAS PIPE SIZE CALCULATIONS, PIPING MATERIALS TO CORRELATE WTHE THE NATURAL GAS GENERATOR ON PLAN
PAGE E100. 2018 IFGC 106.3.1, 402.3, 403
09/16/2024 Fire New Construction REVIEW COMPLETED
09/16/2024 PDSD Application Completeness Express REVIEW COMPLETED