Permit: TC-COM-0725-01397
Permit Details
Status:
Inspections
Type:
Commercial Building
Address:
1651 E GLENN ST UNIT 101
Address NEW:
1651 E GLENN ST UNIT 101
Apply Date:
07/22/2025
Applicant:
Alfred Vega
Description:
REFURBISH DERBY APARTMENTS @ GLENN & ADELAIDE REV1: Kitchen electrical to correct site location(s) and code requirements. Units: 101, 111, 115, 117, 119, 121, 123, 125, 127, 129, 131, 133, and 135
Permit Reviews
Permit Number - TC-COM-0725-01397
Permit Status: Inspections
Permit Description: REFURBISH DERBY APARTMENTS @ GLENN & ADELAIDE
REV1: Kitchen electrical to correct site location(s) and code requirements.
Units: 101, 111, 115, 117, 119, 121, 123, 125, 127, 129, 131, 133, and 135
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 09/09/2025 | COMMERCIAL REVIEW - FULL v.2 | 09/30/2025 | REQUIRES RESUBMIT |
| 11/26/2025 | ADMINISTRATIVE v.1 | 11/26/2025 | REQUIRES RESUBMIT |
| 10/09/2025 | COMMERCIAL REVIEW - FULL v.3 | 10/20/2025 | REQUIRES RESUBMIT |
| 11/10/2025 | ADMINISTRATIVE v.2 | 11/10/2025 | APPROVED |
| 10/29/2025 | COMMERCIAL REVIEW - FULL v.4 | 10/29/2025 | REQUIRES RESUBMIT |
| 11/04/2025 | ADMINISTRATIVE v.1 | 11/04/2025 | REQUIRES RESUBMIT |
| 04/28/2026 | COMMERCIAL REVIEW - FULL REVISION v.1 | 05/27/2026 | APPROVED |
| 04/28/2026 | ADMINISTRATIVE v.2 | 04/28/2026 | APPROVED |
| 10/30/2025 | COMMERCIAL REVIEW - FULL v.5 | 10/31/2025 | APPROVED |
| 07/22/2025 | COMMERCIAL REVIEW - FULL v.1 | 08/14/2025 | REQUIRES RESUBMIT |
| 10/31/2025 | RESTAMP - COMMERCIAL v.1 | 11/04/2025 | APPROVED |
Conditions
Permit Number - TC-COM-0725-01397
Permit Status: Inspections
Permit Description: REFURBISH DERBY APARTMENTS @ GLENN & ADELAIDE
REV1: Kitchen electrical to correct site location(s) and code requirements.
Units: 101, 111, 115, 117, 119, 121, 123, 125, 127, 129, 131, 133, and 135
| Date | Description | Comments |
|---|---|---|
| 11/26/2025 | Unit Numbers and their associated permit to be listed in the address section of the Master Plan located on Permit Number TC-COM-0725-01397. Please submit approved plans without City stamps include Unit Numbers and their associated permit in the address section of the Master Plan. Along with a comment review letter, stating that this is a re-stamp to resolve the addressing issue. | |
| 11/12/2025 | Unit Numbers and their associated permit to be listed in the address section of the Master Plan located on Permit Number TC-COM-0725-01397. Please submit approved plans without City stamps include Unit Numbers and their associated permit in the address section of the Master Plan. Along with a comment review letter, stating that this is a re-stamp to resolve the addressing issue. | |
| 10/31/2025 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. | |
| 07/22/2025 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. |
Outstanding Inspections
Permit Status: Inspections
Permit Number: TC-COM-0725-01397
Permite Description: REFURBISH DERBY APARTMENTS @ GLENN & ADELAIDE
REV1: Kitchen electrical to correct site location(s) and code requirements.
Units: 101, 111, 115, 117, 119, 121, 123, 125, 127, 129, 131, 133, and 135
Total Outstanding Inspections - 14
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/24/2025 | COT - LCPL - Rough Soil | N/A | Not Ready | |
| 01/22/2026 | BULD - Electrical Clearance | N/A | Re-inspection required | 1/22/26: Revision required for changes in conductor size at main panel and location of sub-panel must be appropriately identified on plan set, bond bushings required at raceway, conductors at panel must be protected from abrasion at raceway, EMT must be appropriately secured throughout, |
| 10/07/2026 | COT - LCPL - Gas Pressure Test | N/A | Not Applicable | |
| 10/07/2026 | COT - LCBU - Building Final | N/A | Re-inspection required | 10/7/26: properly secure gas piping at exterior of home, enclosed car port needs repair at siding butting up with concrete, combustion air cannot be used to terminate b-vent, 2-kitchen circuits required, properly cap existing plumbing under kitchen sink, switch covers cannot be cut. Remove all existing wiring at back patio, receptacle spacing throughout,properly cap all vents at roof, enclosed carport has not been permitted and has multiple issues (slab,framing,footings,electrical,structural). |
| 10/07/2026 | COT - LCEL - Electrical Intermediate | N/A | Re-inspection required | 10/7/26: properly secure gas piping at exterior of home, enclosed car port needs repair at siding butting up with concrete, combustion air cannot be used to terminate b-vent, 2-kitchen circuits required, properly cap existing plumbing under kitchen sink, switch covers cannot be cut. Remove all existing wiring at back patio, receptacle spacing throughout,properly cap all vents at roof, enclosed carport has not been permitted and has multiple issues (slab,framing,footings,electrical,structural). |
| 10/07/2026 | COT - LCME - Mechanical Final | N/A | Re-inspection required | 10/7/26: properly secure gas piping at exterior of home, enclosed car port needs repair at siding butting up with concrete, combustion air cannot be used to terminate b-vent, 2-kitchen circuits required, properly cap existing plumbing under kitchen sink, switch covers cannot be cut. Remove all existing wiring at back patio, receptacle spacing throughout,properly cap all vents at roof, enclosed carport has not been permitted and has multiple issues (slab,framing,footings,electrical,structural). |
| 10/07/2026 | COT - LCEL - Outdoor Lighting | N/A | Re-inspection required | 10/7/26: properly secure gas piping at exterior of home, enclosed car port needs repair at siding butting up with concrete, combustion air cannot be used to terminate b-vent, 2-kitchen circuits required, properly cap existing plumbing under kitchen sink, switch covers cannot be cut. Remove all existing wiring at back patio, receptacle spacing throughout,properly cap all vents at roof, enclosed carport has not been permitted and has multiple issues (slab,framing,footings,electrical,structural). |
| 10/07/2026 | COT - LCPL - Plumbing Intermediate | N/A | Re-inspection required | 10/7/26: properly secure gas piping at exterior of home, enclosed car port needs repair at siding butting up with concrete, combustion air cannot be used to terminate b-vent, 2-kitchen circuits required, properly cap existing plumbing under kitchen sink, switch covers cannot be cut. Remove all existing wiring at back patio, receptacle spacing throughout,properly cap all vents at roof, enclosed carport has not been permitted and has multiple issues (slab,framing,footings,electrical,structural). |
| 10/07/2026 | COT - LCEL - Electrical Final | N/A | Re-inspection required | 10/7/26: properly secure gas piping at exterior of home, enclosed car port needs repair at siding butting up with concrete, combustion air cannot be used to terminate b-vent, 2-kitchen circuits required, properly cap existing plumbing under kitchen sink, switch covers cannot be cut. Remove all existing wiring at back patio, receptacle spacing throughout,properly cap all vents at roof, enclosed carport has not been permitted and has multiple issues (slab,framing,footings,electrical,structural). |
| 12/23/2025 | ENGR Engineering Final | N/A | Not Ready | Recall when complete and ready to occupy. |
| 10/07/2026 | COT - LCME - Mechanical Intermediate | N/A | Re-inspection required | 10/7/26: properly secure gas piping at exterior of home, enclosed car port needs repair at siding butting up with concrete, combustion air cannot be used to terminate b-vent, 2-kitchen circuits required, properly cap existing plumbing under kitchen sink, switch covers cannot be cut. Remove all existing wiring at back patio, receptacle spacing throughout,properly cap all vents at roof, enclosed carport has not been permitted and has multiple issues (slab,framing,footings,electrical,structural). |
| 10/07/2026 | COT - BULD - SWG Clearance | N/A | Not Applicable | |
| 10/07/2026 | COT - LCPL - Plumbing Final | N/A | Re-inspection required | 10/7/26: properly secure gas piping at exterior of home, enclosed car port needs repair at siding butting up with concrete, combustion air cannot be used to terminate b-vent, 2-kitchen circuits required, properly cap existing plumbing under kitchen sink, switch covers cannot be cut. Remove all existing wiring at back patio, receptacle spacing throughout,properly cap all vents at roof, enclosed carport has not been permitted and has multiple issues (slab,framing,footings,electrical,structural). |
| 10/07/2026 | COT - LCEL - Grounding/Bonding | N/A | Re-inspection required | 10/7/26: properly secure gas piping at exterior of home, enclosed car port needs repair at siding butting up with concrete, combustion air cannot be used to terminate b-vent, 2-kitchen circuits required, properly cap existing plumbing under kitchen sink, switch covers cannot be cut. Remove all existing wiring at back patio, receptacle spacing throughout,properly cap all vents at roof, enclosed carport has not been permitted and has multiple issues (slab,framing,footings,electrical,structural). |
Completed Inspections
Permit Status: Inspections
Permit Number: TC-COM-0725-01397
Permit Description: REFURBISH DERBY APARTMENTS @ GLENN & ADELAIDE
REV1: Kitchen electrical to correct site location(s) and code requirements.
Units: 101, 111, 115, 117, 119, 121, 123, 125, 127, 129, 131, 133, and 135
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2025 | COT - FCON - Fire - Final | Passed | ||
| 12/23/2025 | TRSP - ROW - Notice of Completion | Passed | ||
| 04/13/2026 | COT - LCPL - Rough Soil | Passed | ||
| 06/10/2026 | BULD - Electrical Clearance | Passed | 06/10/2026 Clearance TEP INCR for panel replacement. |