Inspection Status: Re-inspection required
Inspection History: BULD - Electrical Clearance
Permit Number - TC-COM-0725-01397
Inspection Description - BULD - Electrical Clearance
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2026 | BULD - Electrical Clearance | Re-inspection required | 1/22/26: Revision required for changes in conductor size at main panel and location of sub-panel must be appropriately identified on plan set, bond bushings required at raceway, conductors at panel must be protected from abrasion at raceway, EMT must be appropriately secured throughout, | |
| 12/24/2025 | BULD - Electrical Clearance | Not Ready |