Inspection Status: Re-inspection required
Inspection History: BULD - Electrical Clearance
| Date |
Description |
Inspector |
Results |
Comments |
| 01/22/2026 |
BULD - Electrical Clearance |
|
Re-inspection required |
1/22/26: Revision required for changes in conductor size at main panel and location of sub-panel must be appropriately identified on plan set, bond bushings required at raceway, conductors at panel must be protected from abrasion at raceway, EMT must be appropriately secured throughout, |
| 12/24/2025 |
BULD - Electrical Clearance |
|
Not Ready |
|