Description:
Remove and replace (4) ground-level HVAC units, like for like.

Permit Reviews

Permit Number - TC-COM-0724-01468
Permit Status: Inspections
Permit Description: Remove and replace (4) ground-level HVAC units, like for like.
Start Date Submittal Complete Date Status  
08/01/2024 COMMERCIAL PDSD SIMPLE REVIEW v.1 08/19/2024 REQUIRES RESUBMIT Review Details
08/26/2024 COMMERCIAL PDSD SIMPLE REVIEW v.2 08/29/2024 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-0724-01468
Permit Status: Inspections
Permit Description: Remove and replace (4) ground-level HVAC units, like for like.
Total Outstanding Activity Conditions - 1
Date Name
08/19/2024 AIR BALANCING REPORT IS REQUIRED: OUTSIDE AIR AND SUPPLY AIR FLOW RATES ONLY.

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-COM-0724-01468
Permite Description: Remove and replace (4) ground-level HVAC units, like for like.
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
03/21/2025 COT - LCME - Mechanical Final N/A Re-inspection required 2-25-25, have hvac tech be on site to provide roof access.
3/21/25: condensate drain must be coated for UV protection, properly secure liquid tight at all units, label all disconnect boxes, properly identify heater kit installed in units if used if none are used then units are all being over amped. Smoke detectors not installed on duct work, sun shield required on flex duct.
03/21/2025 BULD - Electrical Clearance N/A Re-inspection required 2-25-25, have hvac tech be on site to provide roof access.
3/21/25: condensate drain must be coated for UV protection, properly secure liquid tight at all units, label all disconnect boxes, properly identify heater kit installed in units if used if none are used then units are all being over amped. Smoke detectors not installed on duct work, sun shield required on flex duct.

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-DOLLAR GENERAL 13199_COOLING LOAD CALCS_V2.PDF DOCUMENTS VIEW
TUCSON, AZ LETTER_V2.PDF DOCUMENTS VIEW