Inspection Status: Re-inspection required
Inspection History: BULD - Electrical Clearance
Permit Number - TC-COM-0724-01468
Inspection Description - BULD - Electrical Clearance
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/25/2025 | BULD - Electrical Clearance | Re-inspection required | 2-25-25, have hvac tech be on site to provide roof access | |
| 03/21/2025 | BULD - Electrical Clearance | Re-inspection required | 2-25-25, have hvac tech be on site to provide roof access. 3/21/25: condensate drain must be coated for UV protection, properly secure liquid tight at all units, label all disconnect boxes, properly identify heater kit installed in units if used if none are used then units are all being over amped. Smoke detectors not installed on duct work, sun shield required on flex duct. |