Parcel: 13708021E


Addresses:

5663 S 12TH AV


Inspection Status: Re-inspection required

Inspection History: COT - LCME - Mechanical Final 

Permit Number - TC-COM-0724-01468

Inspection Description - COT - LCME - Mechanical Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
03/21/2025 COT - LCME - Mechanical Final  Re-inspection required 2-25-25, have hvac tech be on site to provide roof access.
3/21/25: condensate drain must be coated for UV protection, properly secure liquid tight at all units, label all disconnect boxes, properly identify heater kit installed in units if used if none are used then units are all being over amped. Smoke detectors not installed on duct work, sun shield required on flex duct.