Permit: TC-COM-0724-01462
Permit Details
Status:
Inspections
Type:
Commercial Building
Address:
2308 N CAMPBELL AV
Address NEW:
2308 N CAMPBELL AV
Apply Date:
07/30/2024
Applicant:
Andrew Venne
Description:
NARRATIVE SCOPE OF WORK THIS TENANT SPACE HAS HAD MANY USES OVER THE YEARS, THE MOST RECENT USE WAS BICYCLE SALES AND REPAIR. THE OWNER AND TENANT OF THE BUILDING IS SAVAYA COFFEE. THEY SELL COFFEE BEANS AND OTHER RETAIL PRODUCTS AND PROVIDE COFFEE AND TEA TO GO. THEY ALSO SELL PACKAGED DESSERTS. PERMITS PULLED FOR DEMOLITION OF SPACE
Permit Reviews
Permit Number - TC-COM-0724-01462
Permit Status: Inspections
Permit Description: NARRATIVE SCOPE OF WORK
THIS TENANT SPACE HAS HAD MANY USES OVER THE YEARS, THE MOST RECENT USE WAS BICYCLE SALES AND REPAIR. THE OWNER AND TENANT OF THE BUILDING IS SAVAYA COFFEE. THEY SELL COFFEE BEANS AND OTHER RETAIL PRODUCTS AND PROVIDE COFFEE AND TEA TO GO. THEY ALSO SELL PACKAGED DESSERTS.
PERMITS PULLED FOR DEMOLITION OF SPACE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 09/16/2024 | COMMERCIAL REVIEW - FULL v.2 | 10/16/2024 | REQUIRES RESUBMIT |
| 10/22/2024 | RESTAMP - COMMERCIAL v.1 | 10/29/2024 | APPROVED |
| 10/21/2024 | COMMERCIAL REVIEW - FULL v.3 | 10/22/2024 | APPROVED |
| 07/30/2024 | COMMERCIAL REVIEW - FULL v.1 | 08/29/2024 | REQUIRES RESUBMIT |
Outstanding Activity Conditions
Permit Number - TC-COM-0724-01462
Permit Status: Inspections
Permit Description: NARRATIVE SCOPE OF WORK
THIS TENANT SPACE HAS HAD MANY USES OVER THE YEARS, THE MOST RECENT USE WAS BICYCLE SALES AND REPAIR. THE OWNER AND TENANT OF THE BUILDING IS SAVAYA COFFEE. THEY SELL COFFEE BEANS AND OTHER RETAIL PRODUCTS AND PROVIDE COFFEE AND TEA TO GO. THEY ALSO SELL PACKAGED DESSERTS.
PERMITS PULLED FOR DEMOLITION OF SPACE
Total Outstanding Activity Conditions - 5
| Date | Name |
|---|---|
| 09/26/2024 | AIR BALANCING REPORT IS REQUIRED. |
| 09/26/2024 | SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED. |
| 09/26/2024 | SPECIAL INSPECTION FOR EXPANSION ANCHORS IS REQUIRED. |
| 09/26/2024 | Post-Installed Anchor Inspection Report is required. |
| 09/26/2024 | WATER STERILIZATION REPORT IS REQUIRED. |
Outstanding Inspections
Permit Status: Inspections
Permit Number: TC-COM-0724-01462
Permite Description: NARRATIVE SCOPE OF WORK
THIS TENANT SPACE HAS HAD MANY USES OVER THE YEARS, THE MOST RECENT USE WAS BICYCLE SALES AND REPAIR. THE OWNER AND TENANT OF THE BUILDING IS SAVAYA COFFEE. THEY SELL COFFEE BEANS AND OTHER RETAIL PRODUCTS AND PROVIDE COFFEE AND TEA TO GO. THEY ALSO SELL PACKAGED DESSERTS.
PERMITS PULLED FOR DEMOLITION OF SPACE
Total Outstanding Inspections - 8
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2025 | COT - HCBU - Exterior Clips/Sheathing | N/A | Not Applicable | |
| 03/17/2025 | COT - HCME - Mechanical Above Ceiling | N/A | Not Applicable | |
| 03/17/2025 | COT - HCPL - Plumbing Above Ceiling | N/A | Not Applicable | |
| 12/24/2025 | COT - HCBU - Building Final | N/A | Partial Pass | 12/24/25: OKAY FOR LEVEL 1 TCO ( 12/24/25: SWG clearance will not be sent until gas pressure test is conducted, verify bonding of gas piping, sizing and supports, shut-off valves required at all appliance and sediment traps required throughout (roof was not walked during inspection), RTUs must be inspected to verify proper drainage of condensate, verify equipment size and electrical connections. Venting incomplete at roasting stations, GFCI receptacles required with 6' of water source (near water heater and sink in employee area, ADA requirements must be met prior to inspection, Hot water lines at water heater required to be insulated, all disconnect boxes must be labeled, panels must be labeled and panel schedules must be replaced and corrected, air gap required at 3-compartment sink and proper support at plumbing drain. Special inspection reports required prior to final, water sterilization and Pima county health inspection required prior to issuance of TCO above level 1. MORE ITEMS MAY BE ADDED) |
| 10/24/2025 | COT - HCPL - Plumbing Final | N/A | Not Ready | |
| 12/24/2025 | ENGR Engineering Final | N/A | Partial Pass | Okay for level 1 TCO |
| 12/24/2025 | COT - HCEL - Electrical Final | N/A | Re-inspection required | 12/24/25: SWG clearance will not be sent until gas pressure test is conducted, verify bonding of gas piping, sizing and supports, shut-off valves required at all appliance and sediment traps required throughout (roof was not walked during inspection), RTUs must be inspected to verify proper drainage of condensate, verify equipment size and electrical connections. Venting incomplete at roasting stations, GFCI receptacles required with 6' of water source (near water heater and sink in employee area, ADA requirements must be met prior to inspection, Hot water lines at water heater required to be insulated, all disconnect boxes must be labeled, panels must be labeled and panel schedules must be replaced and corrected, air gap required at 3-compartment sink and proper support at plumbing drain. MORE ITEMS MAY BE ADDED. |
| 12/24/2025 | COT - HCME - Mechanical Final | N/A | Re-inspection required | 12/24/25: SWG clearance will not be sent until gas pressure test is conducted, verify bonding of gas piping, sizing and supports, shut-off valves required at all appliance and sediment traps required throughout (roof was not walked during inspection), RTUs must be inspected to verify proper drainage of condensate, verify equipment size and electrical connections. Venting incomplete at roasting stations, GFCI receptacles required with 6' of water source (near water heater and sink in employee area, ADA requirements must be met prior to inspection, Hot water lines at water heater required to be insulated, all disconnect boxes must be labeled, panels must be labeled and panel schedules must be replaced and corrected, air gap required at 3-compartment sink and proper support at plumbing drain. MORE ITEMS MAY BE ADDED. |
Completed Inspections
Permit Status: Inspections
Permit Number: TC-COM-0724-01462
Permit Description: NARRATIVE SCOPE OF WORK
THIS TENANT SPACE HAS HAD MANY USES OVER THE YEARS, THE MOST RECENT USE WAS BICYCLE SALES AND REPAIR. THE OWNER AND TENANT OF THE BUILDING IS SAVAYA COFFEE. THEY SELL COFFEE BEANS AND OTHER RETAIL PRODUCTS AND PROVIDE COFFEE AND TEA TO GO. THEY ALSO SELL PACKAGED DESSERTS.
PERMITS PULLED FOR DEMOLITION OF SPACE
Total Completed Inspections - 16
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/12/2024 | COT - HCPL - Yard Water Line | Passed | New water line along with back flow install. Okay to backfill. Shading required. 12/12/2024 | |
| 03/17/2025 | COT - HCBU - Building Above Ceiling | Passed | ||
| 03/17/2025 | COT - HCBU - Framing | Passed | ||
| 03/17/2025 | COT - HCEL - Electrical Above Ceiling | Passed | ||
| 03/17/2025 | COT - HCEL - Electrical Intermediate | Passed | ||
| 03/17/2025 | COT - HCME - Mechanical Intermediate | Passed | ||
| 03/17/2025 | COT - HCPL - Gas Pressure Test | Passed | ||
| 03/17/2025 | COT - HCPL - Plumbing Intermediate | Passed | ||
| 03/17/2025 | COT - HCPL - Rough Soil | Passed | ||
| 04/29/2025 | BULD - Electrical Clearance | Passed | ECO | |
| 10/24/2025 | TRSP - ROW - Final/Close-Out | Passed | ||
| 12/24/2025 | COT - FCON - Fire - Final | Passed | This inspection was for 2310 n campbell | |
| 12/24/2025 | PDSD Building Division SIte Consultation | Passed | ||
| 12/24/2025 | COT - HCEL - Grounding/Bonding | Passed | ||
| 01/09/2026 | COT - BULD - SWG Clearance | Passed | ||
| 01/09/2026 | COT - HCPL - Gas Final | Passed |