Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Parcel: 123052170


Addresses:

2308 N CAMPBELL AV


Inspection Status: Not Ready

Inspection History: COT - HCPL - Plumbing Final 

Permit Number - TC-COM-0724-01462

Inspection Description - COT - HCPL - Plumbing Final 

Inspection Status - Not Ready

Date Description Inspector Results Comments
10/24/2025 COT - HCPL - Plumbing Final  Not Ready
12/24/2025 COT - HCPL - Plumbing Final  Re-inspection required 12/24/25: SWG clearance will not be sent until gas pressure test is conducted, verify bonding of gas piping, sizing and supports, shut-off valves required at all appliance and sediment traps required throughout (roof was not walked during inspection), RTUs must be inspected to verify proper drainage of condensate, verify equipment size and electrical connections. Venting incomplete at roasting stations, GFCI receptacles required with 6' of water source (near water heater and sink in employee area, ADA requirements must be met prior to inspection, Hot water lines at water heater required to be insulated, all disconnect boxes must be labeled, panels must be labeled and panel schedules must be replaced and corrected, air gap required at 3-compartment sink and proper support at plumbing drain. MORE ITEMS MAY BE ADDED.