Inspection Status: Re-inspection required
Inspection History: COT - HCEL - Electrical Final
Permit Number - TC-COM-0724-01462
Inspection Description - COT - HCEL - Electrical Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/24/2025 | COT - HCEL - Electrical Final | Re-inspection required | 12/24/25: SWG clearance will not be sent until gas pressure test is conducted, verify bonding of gas piping, sizing and supports, shut-off valves required at all appliance and sediment traps required throughout (roof was not walked during inspection), RTUs must be inspected to verify proper drainage of condensate, verify equipment size and electrical connections. Venting incomplete at roasting stations, GFCI receptacles required with 6' of water source (near water heater and sink in employee area, ADA requirements must be met prior to inspection, Hot water lines at water heater required to be insulated, all disconnect boxes must be labeled, panels must be labeled and panel schedules must be replaced and corrected, air gap required at 3-compartment sink and proper support at plumbing drain. MORE ITEMS MAY BE ADDED. |