Permit Details

Status:
Issued
Type:
Commercial Building
Address:
755 E BENSON HY
Apply Date:
06/22/2023
Applicant:
Shane LaLama
Description:
Combine 2 guestrooms into office. Replace exist structural beam. Relocated 2 exist outlets. No change to exist HVAC or plumbing.

Permit Reviews

Permit Number - TC-COM-0623-01560
Permit Status: Issued
Permit Description: Combine 2 guestrooms into office. Replace exist structural beam. Relocated 2 exist outlets. No change to exist HVAC or plumbing.
Start Date Submittal Complete Date Status  
06/28/2023 COMMERCIAL REVIEW - FULL v.1 08/04/2023 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-0623-01560
Permit Status: Issued
Permit Description: Combine 2 guestrooms into office. Replace exist structural beam. Relocated 2 exist outlets. No change to exist HVAC or plumbing.
Total Outstanding Activity Conditions - 2
Date Name
08/02/2023 A fire alarm is required [IBC 907], If they exist...indicate them on your drawing. If not...please propose to install them. Submit the drawings to Tucson Fire Department for review and approval. They will conduct fire inspection, the inspection approval document will be required before issuing the Certificate of Occupancy. Illumination with emergency backup power is required in all components of the means of egress system [IBC 1008]. Electrical work (conductors/wiring/breaker ONLY) related to the installation of Emergency Lights, Lighted Signs, Audible Fire/Smoke Alarms shall be inspected by City of Tucson inspectors [please locate those equipments (to be inspected by the Fire Department) on your plans so that our inspectors will know what wiring/breaker to inspect].
08/02/2023 STATE FIRE MARSHAL INSPECTION IS REQUIRED - PLEASE PROVIDE DOCUMENTATION

Conditions

Permit Number - TC-COM-0623-01560
Permit Status: Issued
Permit Description: Combine 2 guestrooms into office. Replace exist structural beam. Relocated 2 exist outlets. No change to exist HVAC or plumbing.
Date Description Comments
08/04/2023 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.

Outstanding Inspections

Permit Status: Issued
Permit Number: TC-COM-0623-01560
Permite Description: Combine 2 guestrooms into office. Replace exist structural beam. Relocated 2 exist outlets. No change to exist HVAC or plumbing.
Total Outstanding Inspections - 5
Last Inspection Date Description Inspector Results Comments
11/29/2023 COT - FCON - Sprinkler - Final N/A Not Applicable
01/10/2024 COT - LCEL - Electrical Final N/A Re-inspection required 1/10/24: cover plates missing throughout, GFCI required within 6' of water source, panel schedule missing, GFCI at bathroom has no power, receptacle in office has ground and neutral reversed, anti tip missing at range, all light fixtures must be installed, drywall not installed near restroom do to leak on second floor. Needs structural repair on over notched 2x8 at bathroom ceiling.
01/10/2024 COT - LCBU - Building Final N/A Re-inspection required 1/10/24: cover plates missing throughout, GFCI required within 6' of water source, panel schedule missing, GFCI at bathroom has no power, receptacle in office has ground and neutral reversed, anti tip missing at range, all light fixtures must be installed, drywall not installed near restroom do to leak on second floor.
COT - FCON - Fire - Final N/A Not Ready Fire alarm has not been finialed per permit T19FC00703.
COT - FCON - Alarm - Final N/A Not Ready Fire alarm was never tested. Permit T19FC00703

Completed Inspections

Permit Status: Issued
Permit Number: TC-COM-0623-01560
Permit Description: Combine 2 guestrooms into office. Replace exist structural beam. Relocated 2 exist outlets. No change to exist HVAC or plumbing.
Total Completed Inspections - 7
Date Description Inspector Results Comments
11/29/2023 COT - LCBU - Framing Passed
01/10/2024 COT - HCEL - Electrical Intermediate Passed
01/10/2024 COT - LCBU - Excavation/Rebar/Zoning Passed
03/19/2024 COT - LCEL - Electrical Final Passed
04/09/2024 COT - LCBU - Building Final Passed
06/27/2024 COT - FCON - Fire - Final Passed
06/27/2024 COT - FCON - Alarm - Final Passed

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-PDF_230130_211916 (4)-4-COMBINED_1_V1.PDF DOCUMENTS VIEW