Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Re-inspection required
Inspection History: COT - LCEL - Electrical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 01/10/2024 |
COT - LCEL - Electrical Final |
|
Re-inspection required |
1/10/24: cover plates missing throughout, GFCI required within 6' of water source, panel schedule missing, GFCI at bathroom has no power, receptacle in office has ground and neutral reversed, anti tip missing at range, all light fixtures must be installed, drywall not installed near restroom do to leak on second floor. Needs structural repair on over notched 2x8 at bathroom ceiling. |
| 03/19/2024 |
COT - LCEL - Electrical Final |
|
Passed |
|
| 11/29/2023 |
COT - LCEL - Electrical Final |
|
Not Ready |
|