Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - LCEL - Electrical Final
Permit Number - TC-COM-0623-01560
Inspection Description - COT - LCEL - Electrical Final
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/10/2024 | COT - LCEL - Electrical Final | Re-inspection required | 1/10/24: cover plates missing throughout, GFCI required within 6' of water source, panel schedule missing, GFCI at bathroom has no power, receptacle in office has ground and neutral reversed, anti tip missing at range, all light fixtures must be installed, drywall not installed near restroom do to leak on second floor. Needs structural repair on over notched 2x8 at bathroom ceiling. | |
03/19/2024 | COT - LCEL - Electrical Final | Passed | ||
11/29/2023 | COT - LCEL - Electrical Final | Not Ready |