Parcel: 132130500


Addresses:

755 E BENSON HY


Inspection Status: Re-inspection required

Inspection History: COT - LCEL - Electrical Final 

Permit Number - TC-COM-0623-01560

Inspection Description - COT - LCEL - Electrical Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
01/10/2024 COT - LCEL - Electrical Final  Re-inspection required 1/10/24: cover plates missing throughout, GFCI required within 6' of water source, panel schedule missing, GFCI at bathroom has no power, receptacle in office has ground and neutral reversed, anti tip missing at range, all light fixtures must be installed, drywall not installed near restroom do to leak on second floor. Needs structural repair on over notched 2x8 at bathroom ceiling.
03/19/2024 COT - LCEL - Electrical Final  Passed
11/29/2023 COT - LCEL - Electrical Final  Not Ready