Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - LCBU - Building Final
Permit Number - TC-COM-0623-01560
Inspection Description - COT - LCBU - Building Final
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/10/2024 | COT - LCBU - Building Final | Re-inspection required | 1/10/24: cover plates missing throughout, GFCI required within 6' of water source, panel schedule missing, GFCI at bathroom has no power, receptacle in office has ground and neutral reversed, anti tip missing at range, all light fixtures must be installed, drywall not installed near restroom do to leak on second floor. | |
03/19/2024 | COT - LCBU - Building Final | Not Ready | ||
04/09/2024 | COT - LCBU - Building Final | Passed |