Permit: TC-COM-0524-00969
Permit Details
Apply Date:
05/20/2024
Applicant:
Description:
Interior remodel of existing building
Permit Reviews
Permit Number - TC-COM-0524-00969
Permit Status: Complete
Permit Description: Interior remodel of existing building
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 07/15/2024 | RESTAMP - COMMERCIAL v.1 | 07/22/2024 | APPROVED |
| 05/23/2024 | COMMERCIAL REVIEW - LIMITED v.1 | 06/11/2024 | REQUIRES RESUBMIT |
| 06/24/2024 | COMMERCIAL REVIEW - LIMITED v.2 | 07/15/2024 | APPROVED |
| 07/25/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 07/30/2025 | APPROVED |
| 06/25/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 06/25/2025 | APPROVED |
Conditions
Permit Number - TC-COM-0524-00969
Permit Status: Complete
Permit Description: Interior remodel of existing building
| Date | Description | Comments |
|---|---|---|
| 06/10/2024 | AIR BALANCING REPORT IS REQUIRED. | |
| 06/11/2024 | SPECIAL INSPECTION FOR BOLTS INSTALLED IN CONCRETE IS REQUIRED. | |
| 06/11/2024 | SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED. | |
| 05/23/2024 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. | |
| 06/11/2024 | SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED. | |
| 06/11/2024 | SPECIAL INSPECTION FOR EXPANSION ANCHORS IS REQUIRED. | |
| 06/11/2024 | SPECIAL INSPECTION FOR REINFORCING STEEL IS REQUIRED. | |
| 06/10/2024 | WATER STERILIZATION REPORT IS REQUIRED. |
Outstanding Inspections
Permit Status: Complete
Permit Number: TC-COM-0524-00969
Permite Description: Interior remodel of existing building
Total Outstanding Inspections - 6
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2024 | BULD - Electrical Clearance | N/A | Not Ready | |
| 10/30/2024 | COT - LCPL - Gas Pressure Test | N/A | Not Ready | Will reschedule when gas service is complete. |
| 10/30/2024 | COT - LCEL - Grounding/Bonding | N/A | Not Ready | |
| 10/30/2024 | COT - LCEL - Electrical Underground | N/A | Not Ready | |
| 05/22/2025 | COT - HCBU - TCO | N/A | Re-inspection required | 5/22/25: Anti-tip not installed at range, light fixtures must be installed at time of final inspection, Receptacles with no equipment ground are required to be on GFCI receptacles with a label reading “no equipment ground” (406.4(D)(2)), ADA requirements not met at ADA restroom, GFCI required at mechanical room, Air handler is being over amped, mini splits are being over amped, air handler is being over amped, all refrigeration lines must be coated for UV protection, lock out caps at condenser required, exterior receptacle must be WR and GFCi protected. Label all circuits at main panel, Conditions have not been satisfied. |
| 05/22/2025 | COT - LCBU - Building Final | N/A | Re-inspection required | 5/22/25: Anti-tip not installed at range, light fixtures must be installed at time of final inspection, Receptacles with no equipment ground are required to be on GFCI receptacles with a label reading “no equipment ground” (406.4(D)(2)), ADA requirements not met at ADA restroom, GFCI required at mechanical room, Air handler is being over amped, mini splits are being over amped, air handler is being over amped, all refrigeration lines must be coated for UV protection, lock out caps at condenser required, exterior receptacle must be WR and GFCi protected. Label all circuits at main panel, Conditions have not been satisfied. |
Completed Inspections
Permit Status: Complete
Permit Number: TC-COM-0524-00969
Permit Description: Interior remodel of existing building
Total Completed Inspections - 23
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2024 | COT - LCPL - Rough Soil | Passed | Ok to cover progress areas. | |
| 01/03/2025 | BULD - Electrical Clearance | Passed | No clearance required. | |
| 01/03/2025 | COT - LCPL - Gas Pressure Test | Passed | ||
| 01/03/2025 | COT - LCPL - Plumbing Intermediate | Passed | ||
| 01/03/2025 | COT - LCME - Mechanical Intermediate | Passed | ||
| 01/03/2025 | COT - LCEL - Grounding/Bonding | Passed | ||
| 01/03/2025 | COT - LCEL - Electrical Underground | Passed | ||
| 01/03/2025 | COT - LCEL - Electrical Progress | Passed | ||
| 01/03/2025 | COT - LCEL - Electrical Intermediate | Passed | Ok to insulate and cover walls. | |
| 01/03/2025 | COT - LCBU - Roof Nailing | Passed | ||
| 01/03/2025 | COT - LCBU - Preslab | Passed | ||
| 01/03/2025 | COT - LCBU - Framing | Passed | ||
| 01/03/2025 | COT - LCEL - Electrical Above Ceiling | Passed | ||
| 01/03/2025 | COT - LCBU - Excavation/Rebar/Zoning | Passed | ||
| 05/08/2025 | COT - LCEL - Outdoor Lighting | Passed | ||
| 05/27/2025 | COT - FCON - Fire - Final | Passed | ||
| 05/22/2025 | COT - LCME - Mechanical Final | Passed | ||
| 05/22/2025 | ENGR Engineering Final | Passed | At NW corner of building is access to lower crawl space. It is a loose piece of plywood. Should be secured. | |
| 05/22/2025 | COT - LCPL - Plumbing Final | Passed | ||
| 05/22/2025 | COT - LCEL - Electrical Final | Passed | ||
| 05/29/2025 | COT - HCBU - TCO | Passed | All corrections have been completed. 5/29/2025 | |
| 05/29/2025 | COT - LCBU - Building Final | Passed | All corrections have been completed. 5/29/2025 | |
| 06/12/2025 | COT - BULD - SWG Clearance | Passed | 6/12/25: SWG CLEARANCE |