Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - LCBU - Building Final
Permit Number - TC-COM-0524-00969
Inspection Description - COT - LCBU - Building Final
Inspection Status - Not Ready
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2025 | COT - LCBU - Building Final | Not Ready | ||
| 05/22/2025 | COT - LCBU - Building Final | Re-inspection required | 5/22/25: Anti-tip not installed at range, light fixtures must be installed at time of final inspection, Receptacles with no equipment ground are required to be on GFCI receptacles with a label reading “no equipment ground” (406.4(D)(2)), ADA requirements not met at ADA restroom, GFCI required at mechanical room, Air handler is being over amped, mini splits are being over amped, air handler is being over amped, all refrigeration lines must be coated for UV protection, lock out caps at condenser required, exterior receptacle must be WR and GFCi protected. Label all circuits at main panel, Conditions have not been satisfied. | |
| 05/29/2025 | COT - LCBU - Building Final | Passed | All corrections have been completed. 5/29/2025 |