Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - HCBU - TCO
Permit Number - TC-COM-0524-00969
Inspection Description - COT - HCBU - TCO
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2025 | COT - HCBU - TCO | Re-inspection required | 5/22/25: Anti-tip not installed at range, light fixtures must be installed at time of final inspection, Receptacles with no equipment ground are required to be on GFCI receptacles with a label reading “no equipment ground” (406.4(D)(2)), ADA requirements not met at ADA restroom, GFCI required at mechanical room, Air handler is being over amped, mini splits are being over amped, air handler is being over amped, all refrigeration lines must be coated for UV protection, lock out caps at condenser required, exterior receptacle must be WR and GFCi protected. Label all circuits at main panel, Conditions have not been satisfied. | |
| 05/29/2025 | COT - HCBU - TCO | Passed | All corrections have been completed. 5/29/2025 | |
| 10/30/2024 | COT - HCBU - TCO | Not Ready |