Permit Details

Status:
Issued
Type:
Commercial Building
Address NEW:
8750 E GOLF LINKS RD
Apply Date:
05/09/2024
Applicant:
Kevin Barrington
Description:
(1) three story climate controlled self-storage building with site work, MEP and Structural

Permit Reviews

Permit Number - TC-COM-0524-00902
Permit Status: Issued
Permit Description: (1) three story climate controlled self-storage building with site work, MEP and Structural
Start Date Submittal Complete Date Status  
05/14/2024 COMMERCIAL REVIEW - FULL v.1 06/17/2024 REQUIRES RESUBMIT Review Details
08/05/2026 COMMERCIAL REVIEW - FULL v.1 09/02/2026 REQUIRES RESUBMIT Review Details
10/19/2026 COMMERCIAL REVIEW - FULL v.2 N/A IN REVIEW Review Details
07/31/2024 RESTAMP - COMMERCIAL v.1 08/06/2024 APPROVED Review Details
07/08/2025 RESTAMP - COMMERCIAL v.1 07/11/2025 APPROVED Review Details
10/19/2026 BUILDING DEFERRED SUBMITTAL REVIEW v.1 10/20/2026 APPROVED Review Details
06/26/2024 COMMERCIAL REVIEW - FULL v.2 07/31/2024 APPROVED Review Details
06/16/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.1 06/17/2025 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-0524-00902
Permit Status: Issued
Permit Description: (1) three story climate controlled self-storage building with site work, MEP and Structural
Total Outstanding Activity Conditions - 8
Date Name
07/05/2024 SPECIAL INSPECTION FOR BOLTS INSTALLED IN CONCRETE IS REQUIRED.
07/05/2024 SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED.
07/05/2024 SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED.
07/05/2024 SPECIAL INSPECTION FOR EXPANSION ANCHORS IS REQUIRED.
07/05/2024 SPECIAL INSPECTION FOR FIELD WELDING IS REQUIRED.
07/05/2024 SPECIAL INSPECTION FOR SPECIAL GRADING, EXCAVATION AND FILLING IS REQUIRED.
07/05/2024 SPECIAL INSPECTION FOR STRUCTURAL WELDING IS REQUIRED.
07/05/2024 SPECIAL INSPECTION FOR WELDING IS REQUIRED.

Conditions

Permit Number - TC-COM-0524-00902
Permit Status: Issued
Permit Description: (1) three story climate controlled self-storage building with site work, MEP and Structural
Date Description Comments
05/14/2024 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.
05/14/2024 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment.
07/05/2024 A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit.
10/13/2026 WATER STERILIZATION REPORT IS REQUIRED.

Outstanding Inspections

Permit Status: Issued
Permit Number: TC-COM-0524-00902
Permite Description: (1) three story climate controlled self-storage building with site work, MEP and Structural
Total Outstanding Inspections - 21
Last Inspection Date Description Inspector Results Comments
11/21/2025 COT - HCBU - Framing N/A Not Ready Wanted pre-grout
04/09/2026 COT - HCPL - Sewer N/A Partial Pass Main tap
12/03/2025 COT - HCBU - Exterior Clips/Sheathing N/A Partial Pass
08/11/2025 COT - HCBU - Excavation/Rebar/Zoning N/A Partial Pass 8-11-25: reinforcement on the exterior continuous footers stemming from detail's-WF1, MW2, & 4-C2/F2 columns verified per plans. Okay for concrete placement at progress areas.
08/07/2025 COT - HCEL - Electrical Underground N/A Partial Pass Conduits at electric room.
08/18/2025 BULD - Electrical Clearance N/A Partial Pass 8-18-25: okay to energize panel-temp power(TMPP)clearance issued to TEP.
08/28/2025 COT - HCEL - Grounding/Bonding N/A Partial Pass Ufer connection to rebar.
05/07/2026 COT - HCPL - Plumbing Intermediate N/A Re-inspection required Provide test for water piping
09/01/2026 COT - HCME - Mechanical Underground N/A Not Applicable
04/16/2026 COT - HCBU - Sustainability N/A Partial Pass Starting dens glass
10/14/2026 COT - HCME - Mechanical Final N/A Re-inspection required 10/14/26: Heat-kit has to be marked on label if installed to verify proper fuses. (Only walked 1st floor)
07/24/2025 COT - HCEL - Electrical Intermediate N/A Re-inspection required Pre con meeting. 7/24/2025
10/14/2026 COT - FCON - Alarm - Final N/A Partial Pass Tested FACP Smoke, Pull Station, Water Flow and Tamper. All reported to panel and central station. Awaiting elevator test completion to verify elevator recall.
COT - FCON - Sprinkler - Final N/A Not Ready Underground fire line permit shall be applied for.
09/01/2026 COT - HCME - Mechanical Intermediate N/A Canceled
10/14/2026 COT - FCON - Fire - Final N/A Partial Pass Tested FACP Smoke, Pull Station, Water Flow and Tamper. All reported to panel and central station. Awaiting elevator test completion to verify elevator recall. Ok for Level 3 TCO for First Floor.
10/14/2026 COT - HCPL - Plumbing Final N/A Re-inspection required 10/14/26: Heat-kit has to be marked on label if installed to verify proper fuses. (Only walked 1st floor), ADA requirements at break room (receptacles must be surface mounted to meet reach range), ada signage required at bathrooms, lobby area counter space for ADA required. (1st floor walked only)
10/21/2026 ENGR Engineering Final N/A Partial Pass Okay to apply for Level 3 TCO - 1st Floor Only
10/22/2026 COT - HCBU - Building Final N/A Partial Pass 10.22.26-2nd floor walked; okay for level 3 TCO please block off elevators until certified.
10/23/2026 COT - HCEL - Electrical Final N/A Partial Pass 10/23/26
3rd floor walked, okay for level 3 TCO, Elevators must remain blocked off until certified.
10/30/2026 COT - HCBU - CofO N/A Canceled

Completed Inspections

Permit Status: Issued
Permit Number: TC-COM-0524-00902
Permit Description: (1) three story climate controlled self-storage building with site work, MEP and Structural
Total Completed Inspections - 29
Date Description Inspector Results Comments
10/29/2025 COT - HCPL - Rough Soil Passed Underground plumbing per plan, ok to backfill
12/12/2025 COT - HCBU - Masonry Pregrout Passed 12/12/25 complete
02/26/2026 COT - HCBU - Preslab Passed
04/09/2026 COT - HCBU - Framing Passed Levels Two and Three
04/14/2026 COT - HCPL - Sewer Passed
04/17/2026 COT - HCPL - Yard Water Line Passed
04/29/2026 COT - HCBU - Roof Nailing Passed Passed 4/28/26
05/07/2026 COT - HCBU - Exterior Clips/Sheathing Passed
05/11/2026 COT - HCPL - Plumbing Progress Passed Passed 5/11/26, pressure tested
05/12/2026 COT - HCBU - Excavation/Rebar/Zoning Passed Trash enclosure; instructed contractor to schedule Engineering inspection for location.
05/13/2026 COT - HCEL - Electrical Underground Passed
06/10/2026 BULD - Electrical Clearance Passed 6.10.26
TEP CLEARANCE: ECO
08/14/2026 COT - HCBU - Building Above Ceiling Passed
08/13/2026 COT - HCEL - Electrical Progress Passed
08/14/2026 COT - HCBU - Building Progress Passed
08/14/2026 COT - HCME - Mechanical Above Ceiling Passed
08/14/2026 COT - HCEL - Grounding/Bonding Passed
08/14/2026 COT - HCPL - Plumbing Intermediate Passed
08/27/2026 COT - HCME - Mechanical Progress Passed Duct sealing.
10/13/2026 COT - HCPL - Backwater Valve Passed
10/14/2026 COT - HCBU - Sustainability Passed
10/14/2026 COT - HCEL - Electrical Intermediate Passed
10/14/2026 COT - HCEL - Electrical Above Ceiling Passed
10/14/2026 TRSP - ROW - Notice of Completion Passed Work completed outside of the city right of way
10/14/2026 COT - HCME - Mechanical Intermediate Passed
10/14/2026 COT - HCBU - Firewall/Fire Barrier/Firestop Passed
10/14/2026 COT - HCEL - Outdoor Lighting Passed
10/14/2026 COT - HCPL - Plumbing Roof Drains Passed
10/14/2026 COT - HCPL - Plumbing Above Ceiling Passed

Documents

File Name Document Type  
26J2278 LTS_NOQC3 COC REV TUCSON PDF FINAL 10 15 26 1542-2026-10-19_V1.PDF DOCUMENTS VIEW
GOLF LINKS STORAGE STRUCTURAL CALCS_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
SPECIAL_INSPECTION_CERTIFICATE_MEP_V1.PDF DOCUMENTS VIEW
SPECIAL_INSPECTION_CERTIFICATE_ODL_V1.PDF DOCUMENTS VIEW
SPECIAL_INSPECTION_CERTIFICATE_STRUCTURAL-2025-06-16_V1.PDF DOCUMENTS VIEW
CONS-GOLF LINKS 2ND SUB SET_V2.PDF DOCUMENTS VIEW