Permit: TC-COM-0523-01238
Permit Details
Apply Date:
05/09/2023
Applicant:
Arnulfo Grijalva
Description:
Interior tenant improvement to an existing building for a new restaurant
Permit Reviews
Permit Number - TC-COM-0523-01238
Permit Status: Issued
Permit Description: Interior tenant improvement to an existing building for a new restaurant
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
07/26/2023 | RESTAMP - COMMERCIAL v.1 | 07/27/2023 | APPROVED |
05/12/2023 | COMMERCIAL REVIEW - FULL v.1 | 06/15/2023 | REQUIRES RESUBMIT |
07/25/2023 | COMMERCIAL REVIEW - FULL v.3 | 07/26/2023 | APPROVED |
07/07/2023 | COMMERCIAL REVIEW - FULL v.2 | 07/13/2023 | REQUIRES RESUBMIT |
Conditions
Permit Number - TC-COM-0523-01238
Permit Status: Issued
Permit Description: Interior tenant improvement to an existing building for a new restaurant
Date | Description | Comments |
---|---|---|
05/12/2023 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. |
Outstanding Inspections
Permit Status: Issued
Permit Number: TC-COM-0523-01238
Permite Description: Interior tenant improvement to an existing building for a new restaurant
Total Outstanding Inspections - 8
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/01/2024 | COT - HCPL - Plumbing Progress | N/A | Partial Pass | 3/1/24: plumbing underground per plan ok to backfill. |
04/10/2024 | COT - HCPL - Gas Final | N/A | Not Ready | |
04/15/2024 | COT - HCME - Mechanical Intermediate | N/A | Partial Pass | |
05/01/2024 | COT - HCBU - Building Above Ceiling | N/A | Re-inspection required | 5/1/24: j-boxes not made up and faceplates missing, unused knock-out must be sealed at j-boxes. Supports missing at registers, kitchen hood failed smoke test. |
05/01/2024 | COT - HCME - Mechanical Above Ceiling | N/A | Re-inspection required | Ductwork sealed and ok to wrap 5/1/24: seismic wire missing at registers |
05/13/2024 | COT - HCEL - Electrical Above Ceiling | N/A | Canceled | 5/13/24: canceled per contractor |
05/13/2024 | COT - HCEL - Electrical Final | N/A | Canceled | 5/13/24: canceled per contractor |
05/01/2024 | COT - HCME - Kitchen Hood | N/A | Re-inspection required | Not ready 4/15/24 hood up to smoke test 5/1/24: smoke test not passed. Leaking throughout |
Completed Inspections
Permit Status: Issued
Permit Number: TC-COM-0523-01238
Permit Description: Interior tenant improvement to an existing building for a new restaurant
Total Completed Inspections - 11
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/01/2024 | COT - HCPL - Rough Soil | Passed | 3/1/24: plumbing underground per plan ok to backfill. | |
03/06/2024 | COT - HCBU - Building Progress | Passed | ||
03/20/2024 | COT - HCEL - Electrical Intermediate | Passed | ||
03/20/2024 | COT - HCPL - Plumbing Intermediate | Passed | ok for dry wall | |
04/04/2024 | COT - HCBU - Framing | Passed | ||
04/10/2024 | COT - BULD - SWG Clearance | Passed | ||
04/10/2024 | COT - HCPL - Gas Pressure Test | Passed | ||
04/10/2024 | COT - HCEL - Electrical Progress | Passed | ||
04/15/2024 | COT - HCME - Mechanical Progress | Passed | ||
05/01/2024 | COT - HCPL - Plumbing Above Ceiling | Passed | ||
05/14/2024 | BULD - Electrical Clearance | Passed | 5/13/24: canceled per contractor 5/14/24: ECO TEP CLEARANCE for 3470 S. KINO PARKWAY TENANT-1 SUITE- 180 |