Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Inspections
Type:
Commercial Building
Address NEW:
4101 N CAMPBELL AV
Apply Date:
03/12/2025
Applicant:
Austin Matson
Description:
INSTALLATION OF 105.6KWDC GROUND MOUNTED SOLAR PANEL SYSTEM ON SINGLE AXIS TRACKER

Permit Reviews

Permit Number - TC-COM-0325-00489
Permit Status: Inspections
Permit Description: INSTALLATION OF 105.6KWDC GROUND MOUNTED SOLAR PANEL SYSTEM ON SINGLE AXIS TRACKER
Start Date Submittal Complete Date Status  
05/19/2025 COMMERCIAL REVIEW - FULL v.2 06/06/2025 APPROVED Review Details
03/13/2025 COMMERCIAL REVIEW - FULL v.1 04/07/2025 REQUIRES RESUBMIT Review Details
06/06/2025 RESTAMP - COMMERCIAL v.1 06/06/2025 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-0325-00489
Permit Status: Inspections
Permit Description: INSTALLATION OF 105.6KWDC GROUND MOUNTED SOLAR PANEL SYSTEM ON SINGLE AXIS TRACKER
Total Outstanding Activity Conditions - 3
Date Name
06/06/2025 SPECIAL INSPECTION FOR HIGH STRENGTH BOLTING IS REQUIRED.
06/06/2025 SPECIAL INSPECTION FOR PILING, DRILLED PIERS AND CAISSONS IS REQUIRED.
06/06/2025 SPECIAL INSPECTION FOR SPECIAL MOMENT RESISTING STEEL FRAMES IS REQUIRED.

Conditions

Permit Number - TC-COM-0325-00489
Permit Status: Inspections
Permit Description: INSTALLATION OF 105.6KWDC GROUND MOUNTED SOLAR PANEL SYSTEM ON SINGLE AXIS TRACKER
Date Description Comments
06/06/2025 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.
06/06/2025 A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit.

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-COM-0325-00489
Permite Description: INSTALLATION OF 105.6KWDC GROUND MOUNTED SOLAR PANEL SYSTEM ON SINGLE AXIS TRACKER
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
02/03/2026 BULD - Electrical Clearance N/A Partial Pass 02/03/2026
Clearance TEP DGL at 12:50pm for line side tap to existing switchgear box with 150A fused disconnect. Partial pass pending solar final.
02/04/2026 COT - CSOL - Electrical Underground Solar Project N/A Partial Pass 02/04/2026
Partial pass pending other progress areas. Verified next 83ft section run of 36" depth trench with (2) 1.5" & (3) 1" schedule 40 conduit. Verified (2) 65ft runs of trench under arrays with (3) 1" and (2) 1.5" schedule 40 conduit. Okay to backfill with shading and caution burial tape above.

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
COMMENT RESPONSE LETTER_V1.PDF DOCUMENTS VIEW
CONS-PLANSET_2_V2_V3.PDF DOCUMENTS VIEW
COT SIC UA AGRIVOLTAICS PV SOLAR-2025-05-16_V1.PDF DOCUMENTS VIEW
STRUCT CALCS_2_V1.PDF DOCUMENTS VIEW