Permit: T99CM05883
Permit Details
Apply Date:
12/20/1999
Applicant:
STOUFFER CONSTRUCTION COMPANY ,
Description:
TWO STORY W/ BASEMENT OFFICE BUILDING
Contractors:
- STOUFFER CONSTRUCTION COMPANY ,
Completed Inspections
Permit Status: C of o
Permit Number: T99CM05883
Permit Description: TWO STORY W/ BASEMENT OFFICE BUILDING
Total Completed Inspections - 28
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/24/2000 | PLUMBING - SEWER HCS CONNECT | TRINIVJR | Approved | ADDTL COMMS - 1. SOIL WATER TEST OK 2. HCS CONNECTION OK 3. OK TO BACKFILL TRENCH |
05/09/2000 | PLUMBING - ROUGH, SOIL | TRINIVJR | Approved | IVRS - Inspection 0000* |
05/09/2000 | PLUMBING - ROUGH, SOIL | TRINIVJR | Approved | ADDTL COMMS - 1. SOIL WATER TEST 2 ND FLOOR ROUGH OK 2. 1ST FLOOR INTERMEDIATE OK WASTE AND VENT WATER DISTRIBUTION OK. |
05/22/2000 | PLUMBING - INTERMEDIATE | TRINIVJR | Approved | IVRS - Inspection 0000* |
05/22/2000 | PLUMBING - INTERMEDIATE | TRINIVJR | Approved | ADDTL COMMS - 1. WASTE AND VENT SYSTEM OK FOR 2ND FLOOR RESTROOMS 2. OVERHEAD WATER DISTRIBUTION OK 3. OK FOR DRYWALL |
05/31/2000 | PLUMBING - YARD WTR LINE/TEST | TRINIVJR | Approved | ADDTL COMMS - 1. WATER SERVICE FROM METER TO BLDG SERVICE OK BACKFLOW PREVENTER OK 2. OK TO BACKFILL TRENCH |
06/02/2000 | PLUMBING - ABOVE CEILING | TRINIVJR | Approved | ADDTL COMMS - 1. RAIN LEADER, AREA DRAINS WATER TEST OK |
06/21/2000 | SHEET ROCK NAILING | EMONAHAN | Approved | PARTIAL APPROVAL |
06/21/2000 | SHEET ROCK NAILING | EMONAHAN | Approved | ADDTL COMMS - AT 2 FLOOR STAIRWALLS |
07/10/2000 | MECHANICAL - ABOVE CEILING | CWILLIAM | Approved | IVRS - Inspection 0000* |
07/12/2000 | ELECTRIC - CABLE DROP | DSANTACR | Approved | IVRS - Inspection 0000* OK TO CLEAR, TEMP POWER (BOND POSTED) 3636 E. SPEEDWAY SERVICE ONLY |
07/21/2000 | BUILDING ABOVE CEILING | EMONAHAN | Approved | |
08/08/2000 | PLUMBING - FINAL | TRINIVJR | Approved | IVRS - Inspection 0000* APPR TEMP C OF O BASEMENT KIT SINK MUST BE CAULKED WOMENS H.C. WATER CLOSET HANDLE MUST BE ON OPEN SIDE OF STALL (ADA SPECS) WOMENS H.C. LAV MUST BE WRAPPED AND PROVIDE LISTING FOR H.C LAV FAUCET MENS H.C. WATER CLOSET HANDLE MUST BE ON OPEN SIDE OF STALL AGA SPECS IN BASEMENT AND 1ST & 2ND FLOOR URINAL DISCHARGE TUBE MUST BE MIN OF 6" FROM CL CEVEL TO TOP OF FIXTURE IN BASEMENT AND 1ST AND 2ND FLOOR BASEMENT DRINKING FOUNTAIN NOT INSTALLED AT THIS TIME MUST STRAP 2" VENT FOR SEWER EJECTION PIT MUST HAVE HANGER 18" MIN FROM COUPLINGS ON 2" DISCHARGE WASTE LINE ON HORIZONTAL RUN SPRINKLAR SYSTEM DRAIN LINE MUST HAVE PROPER TRANSISTION AT CONNECITON TO ABS MUST CAULK BAC SINK 1ST FL AND 2ND FLOOR 1ST FLOOR H.C. URINAL LIP MUST BE 17" AFF MAX OK FOR TEMP C OF O NOTE BACKFLOW REVENTER MUST BE TESTED AND CERTIFIED PRIOR TO FINAL |
08/08/2000 | ELECTRIC - FINAL | DSANTACR | Approved | OK FOR TEMP C/O |
08/08/2000 | ELECTRIC - FINAL | DSANTACR | Approved | IVRS - Inspection 0000* EMT CONDUIT NOT APPROVED FOR OUTSIDE GROUND INSTALLATION INSTALL WALL PACKS LIGHTING OUTSIDE INSTALL LIGHT SWITCH UPPER STRAIRWAY ROOF HATCH LOCATION DISCONNECT SWITCHES NEED WORKING CLEARANCE 30" HORIZONTAL 36" IN FRONT GENERAL POSTED BOND FOR C OF O OK TEMP OCCUPANCY |
08/08/2000 | BUILDING - FINAL | EMONAHAN | Approved | OK FOR TEMP C OF O |
08/10/2000 | LANDSCAPE - FINAL | LANDSCAP | Approved | OK FOR TEMP C/O |
08/11/2000 | FIRE - FINAL | FIRE | Approved | OK FOR TEMP C/O |
06/01/2001 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | |
06/01/2001 | PERMIT FINALED | FIRE | Approved | |
06/01/2001 | FIRE SPKLR - OH PIPING & HYDRO | FIRE | Approved | |
06/01/2001 | FIRE SPKLR - UG PIPING FLUSH | FIRE | Approved | |
06/01/2001 | FIRE SPKLR - UG, PIPING, HYDRO | FIRE | Approved | |
06/01/2001 | ELECTRIC - UFER | DSANTACR | Approved | |
06/01/2001 | U VALUE FOR WINDOW | AMATHIES | Approved | |
06/01/2001 | REINFORCED MASONRY PRE-GROUT | AMATHIES | Approved | |
06/01/2001 | STEM WALL/RETAINING WALL | AMATHIES | Approved | |
06/01/2001 | EXCAVATION/LAYOUT REBAR & ZON | AMATHIES | Approved |