Permit: T99CM05883

Parcel: 125110630


Addresses:

3636 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T99CM05883

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/03/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000*
08/08/2000 PLUMBING - FINAL Partial Approval IVRS - Inspection 0000*
APPR TEMP C OF O
BASEMENT KIT SINK MUST BE CAULKED
WOMENS H.C. WATER CLOSET HANDLE MUST BE ON OPEN SIDE OF STALL (ADA SPECS)
WOMENS H.C. LAV MUST BE WRAPPED AND PROVIDE LISTING FOR H.C LAV FAUCET
MENS H.C. WATER CLOSET HANDLE MUST BE ON OPEN SIDE OF STALL AGA SPECS IN BASEMENT AND 1ST & 2ND FLOOR
URINAL DISCHARGE TUBE MUST BE MIN OF 6" FROM CL CEVEL TO TOP OF FIXTURE IN BASEMENT AND 1ST AND 2ND FLOOR
BASEMENT DRINKING FOUNTAIN NOT INSTALLED AT THIS TIME
MUST STRAP 2" VENT FOR SEWER EJECTION PIT
MUST HAVE HANGER 18" MIN FROM COUPLINGS ON 2" DISCHARGE WASTE LINE ON HORIZONTAL RUN
SPRINKLAR SYSTEM DRAIN LINE MUST HAVE PROPER TRANSISTION AT CONNECITON TO ABS
MUST CAULK BAC SINK 1ST FL AND 2ND FLOOR
1ST FLOOR H.C. URINAL LIP MUST BE 17" AFF MAX
OK FOR TEMP C OF O
NOTE BACKFLOW REVENTER MUST BE TESTED AND CERTIFIED PRIOR TO FINAL