Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T99CM05883
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/03/2001 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
08/08/2000 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection 0000* APPR TEMP C OF O BASEMENT KIT SINK MUST BE CAULKED WOMENS H.C. WATER CLOSET HANDLE MUST BE ON OPEN SIDE OF STALL (ADA SPECS) WOMENS H.C. LAV MUST BE WRAPPED AND PROVIDE LISTING FOR H.C LAV FAUCET MENS H.C. WATER CLOSET HANDLE MUST BE ON OPEN SIDE OF STALL AGA SPECS IN BASEMENT AND 1ST & 2ND FLOOR URINAL DISCHARGE TUBE MUST BE MIN OF 6" FROM CL CEVEL TO TOP OF FIXTURE IN BASEMENT AND 1ST AND 2ND FLOOR BASEMENT DRINKING FOUNTAIN NOT INSTALLED AT THIS TIME MUST STRAP 2" VENT FOR SEWER EJECTION PIT MUST HAVE HANGER 18" MIN FROM COUPLINGS ON 2" DISCHARGE WASTE LINE ON HORIZONTAL RUN SPRINKLAR SYSTEM DRAIN LINE MUST HAVE PROPER TRANSISTION AT CONNECITON TO ABS MUST CAULK BAC SINK 1ST FL AND 2ND FLOOR 1ST FLOOR H.C. URINAL LIP MUST BE 17" AFF MAX OK FOR TEMP C OF O NOTE BACKFLOW REVENTER MUST BE TESTED AND CERTIFIED PRIOR TO FINAL |