Permit: T99CM05883

Parcel: 125110630


Addresses:

3636 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T99CM05883

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/23/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
05/03/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* 1) LABEL PANELS ETC PER SHEET E.01 SPEC'S #19
08/08/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
EMT CONDUIT NOT APPROVED FOR OUTSIDE GROUND INSTALLATION
INSTALL WALL PACKS LIGHTING OUTSIDE
INSTALL LIGHT SWITCH UPPER STRAIRWAY ROOF HATCH LOCATION
DISCONNECT SWITCHES NEED WORKING CLEARANCE 30" HORIZONTAL 36" IN FRONT
GENERAL POSTED BOND FOR C OF O OK TEMP OCCUPANCY
08/08/2000 ELECTRIC - FINAL Partial Approval OK FOR TEMP C/O