Permit: T22CM05735
Permit Details
Status:
Complete
Type:
Residential Building - One or Two Family
Address:
1952 W KING AV
Address NEW:
1952 W KING AV
Apply Date:
07/28/2022
Applicant:
Description:
SFR
Permit Reviews
Permit Number - T22CM05735
Permit Status: Complete
Permit Description: SFR
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 07/28/2022 | RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO | 08/26/2022 | COMPLETED |
| 01/04/2023 | RESIDENTIAL NEW DWELLING v.1 | 01/12/2023 | REQUIRES RESUBMIT |
| 10/30/2024 | RESIDENTIAL NEW DWELLING v.1 | 10/30/2024 | REQUIRES RESUBMIT |
| 11/04/2024 | RESIDENTIAL NEW DWELLING v.2 | 11/25/2024 | REQUIRES RESUBMIT |
| 02/15/2024 | RESIDENTIAL NEW DWELLING v.4 | 03/18/2024 | APPROVED |
| 01/26/2024 | RESIDENTIAL NEW DWELLING v.3 | 01/26/2024 | REQUIRES RESUBMIT |
| 12/26/2023 | RESIDENTIAL NEW DWELLING v.2 | 01/08/2024 | REQUIRES RESUBMIT |
Conditions
Permit Number - T22CM05735
Permit Status: Complete
Permit Description: SFR
| Date | Description | Comments |
|---|---|---|
| 03/18/2024 | The Contractor you have added to your permit cannot be verified. Please contact staff to have the ROC number added to the account. | |
| 03/18/2024 | Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/pdsd_owner_builder_affidavit_081623.pdf, is required prior to issuance of permit. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit. |
Outstanding Inspections
Permit Status: Complete
Permit Number: T22CM05735
Permite Description: SFR
Total Outstanding Inspections - 10
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/17/2024 | RSBU - Building Final | N/A | Re-inspection required | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. 4/26/24: per previous notes 5/17/24: called Mark at 9:25am (no answer and left message), arrived onsite at 9:40 (called again, no answer), no access to site. |
| 04/12/2024 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | N/A | Re-inspection required | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. |
| 04/12/2024 | COT - RSBU - Roof Nailing | N/A | Re-inspection required | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. |
| 04/12/2024 | COT - RSEL - Electrical Final | N/A | Re-inspection required | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. |
| 04/12/2024 | COT - RSEL - Electrical Underground | N/A | Re-inspection required | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. |
| 04/12/2024 | COT - RSEL - Grounding/Bonding | N/A | Re-inspection required | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. |
| 04/12/2024 | COT - RSME - Mechanical Final | N/A | Re-inspection required | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. |
| 04/12/2024 | COT - RSPL - Yard Water Line | N/A | Re-inspection required | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. |
| 04/12/2024 | COT - RSPL - Plumbing Final | N/A | Re-inspection required | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. |
| 04/12/2024 | COT - RSPL - Rough Soil | N/A | Re-inspection required | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. |
Completed Inspections
Permit Status: Complete
Permit Number: T22CM05735
Permit Description: SFR
Total Completed Inspections - 13
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/17/2024 | RSBU - Building Final | Passed | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. 5/17/24: Contractor letter provided stating that all work preformed meets or exceeds the requirements of the 2018 IRC. All code violations called out at previous inspections have been addressed and corrected. Certificate of Occupancy will be granted with the following conditions: Homeowner will revise and submit future expansion of Home to the City of Tucson within 6 months. |
|
| 05/17/2024 | COT - RSBU - Excavation/Rebar/Zoning | Passed | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. 5/17/24: Contractor letter provided stating that all work preformed meets or exceeds the requirements of the 2018 IRC. All code violations called out at previous inspections have been addressed and corrected. Certificate of Occupancy will be granted with the following conditions: Homeowner will revise and submit future expansion of Home to the City of Tucson within 6 months. |
|
| 05/17/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. 5/17/24: Contractor letter provided stating that all work preformed meets or exceeds the requirements of the 2018 IRC. All code violations called out at previous inspections have been addressed and corrected. Certificate of Occupancy will be granted with the following conditions: Homeowner will revise and submit future expansion of Home to the City of Tucson within 6 months. |
|
| 05/17/2024 | COT - RSBU - Preslab | Passed | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. 5/17/24: Contractor letter provided stating that all work preformed meets or exceeds the requirements of the 2018 IRC. All code violations called out at previous inspections have been addressed and corrected. Certificate of Occupancy will be granted with the following conditions: Homeowner will revise and submit future expansion of Home to the City of Tucson within 6 months. |
|
| 05/17/2024 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. 5/17/24: Contractor letter provided stating that all work preformed meets or exceeds the requirements of the 2018 IRC. All code violations called out at previous inspections have been addressed and corrected. Certificate of Occupancy will be granted with the following conditions: Homeowner will revise and submit future expansion of Home to the City of Tucson within 6 months. |
|
| 05/17/2024 | COT - RSBU - Roof Nailing | Passed | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. 5/17/24: Contractor letter provided stating that all work preformed meets or exceeds the requirements of the 2018 IRC. All code violations called out at previous inspections have been addressed and corrected. Certificate of Occupancy will be granted with the following conditions: Homeowner will revise and submit future expansion of Home to the City of Tucson within 6 months. |
|
| 05/17/2024 | COT - RSEL - Electrical Final | Passed | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. 5/17/24: Contractor letter provided stating that all work preformed meets or exceeds the requirements of the 2018 IRC. All code violations called out at previous inspections have been addressed and corrected. Certificate of Occupancy will be granted with the following conditions: Homeowner will revise and submit future expansion of Home to the City of Tucson within 6 months. |
|
| 05/17/2024 | COT - RSEL - Electrical Underground | Passed | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. 5/17/24: Contractor letter provided stating that all work preformed meets or exceeds the requirements of the 2018 IRC. All code violations called out at previous inspections have been addressed and corrected. Certificate of Occupancy will be granted with the following conditions: Homeowner will revise and submit future expansion of Home to the City of Tucson within 6 months. |
|
| 05/17/2024 | COT - RSEL - Grounding/Bonding | Passed | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. 5/17/24: Contractor letter provided stating that all work preformed meets or exceeds the requirements of the 2018 IRC. All code violations called out at previous inspections have been addressed and corrected. Certificate of Occupancy will be granted with the following conditions: Homeowner will revise and submit future expansion of Home to the City of Tucson within 6 months. |
|
| 05/17/2024 | COT - RSME - Mechanical Final | Passed | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. 5/17/24: Contractor letter provided stating that all work preformed meets or exceeds the requirements of the 2018 IRC. All code violations called out at previous inspections have been addressed and corrected. Certificate of Occupancy will be granted with the following conditions: Homeowner will revise and submit future expansion of Home to the City of Tucson within 6 months. |
|
| 05/17/2024 | COT - RSPL - Yard Water Line | Passed | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. 5/17/24: Contractor letter provided stating that all work preformed meets or exceeds the requirements of the 2018 IRC. All code violations called out at previous inspections have been addressed and corrected. Certificate of Occupancy will be granted with the following conditions: Homeowner will revise and submit future expansion of Home to the City of Tucson within 6 months. |
|
| 05/17/2024 | COT - RSPL - Plumbing Final | Passed | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. 5/17/24: Contractor letter provided stating that all work preformed meets or exceeds the requirements of the 2018 IRC. All code violations called out at previous inspections have been addressed and corrected. Certificate of Occupancy will be granted with the following conditions: Homeowner will revise and submit future expansion of Home to the City of Tucson within 6 months. |
|
| 05/17/2024 | COT - RSPL - Rough Soil | Passed | 4/12/24: Two circuits missing at kitchen, receptacles at exterior need to be WR, missing weather cover at exterior receptacles, bank plate missing at main panel, properly label all panels, properly secure exterior conduit to house, hose bib needs to be properly insulated and UV coated, T&P needs to be installed at Water heater, all exterior pipes need to be coated for UV protection, Bathtub pump needs to be grounded, GFCI at bathtub not working properly, HVAC is being over Amped (30 max), (Mechanical, Plumbing, Electrical, framing, contractor)Letters will be required prior to final stating that all work done meets or exceeds the requirements of the 2018 IRC. More items may be added. 5/17/24: Contractor letter provided stating that all work preformed meets or exceeds the requirements of the 2018 IRC. All code violations called out at previous inspections have been addressed and corrected. Certificate of Occupancy will be granted with the following conditions: Homeowner will revise and submit future expansion of Home to the City of Tucson within 6 months. |