Permit: T22CM01074
Permit Details
Status:
Issued
Type:
Residential Building - One or Two Family
Address:
1364 W SENTINEL VIEW LP
Address NEW:
1364 W SENTINEL VIEW LP
Apply Date:
02/11/2022
Applicant:
Description:
SFR MPLAN1510 T20-M0040
Permit Reviews
Permit Number - T22CM01074
Permit Status: Issued
Permit Description: SFR MPLAN1510 T20-M0040
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 02/11/2022 | RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO | 03/08/2022 | COMPLETED |
| 06/10/2022 | RESUBMITTAL | 06/17/2022 | COMPLETED |
| 05/15/2025 | RESIDENTIAL NEW DWELLING v.1 | 06/17/2025 | APPROVED |
| 08/12/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 08/14/2025 | REQUIRES RESUBMIT |
| 08/19/2025 | BUILDING DEFERRED SUBMITTAL REVIEW v.2 | 08/20/2025 | APPROVED |
| 03/08/2024 | RESIDENTIAL NEW DWELLING v.1 | 03/21/2024 | APPROVED |
Conditions
Permit Number - T22CM01074
Permit Status: Issued
Permit Description: SFR MPLAN1510 T20-M0040
| Date | Description | Comments |
|---|---|---|
| 02/11/2022 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. | |
| 10/09/2024 | The Contractor you have added to your permit cannot be verified. Please contact staff to have the ROC number added to the account. | |
| 10/09/2024 | Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/pdsd_owner_builder_affidavit_081623.pdf, is required prior to issuance of permit. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit. | |
| 01/21/2025 | SPECIAL INSPECTION FOR POST TENSION SLAB IS REQUIRED. | |
| 03/21/2024 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment. | |
| 01/21/2025 | Sewer condition must be accepted and released by Pima County prior to issuance of a Temporary Certificate of Occupancy. For More Information visit https://www.pima.gov/1076/Sewer-Connection-Permits, To check your permit status https://permits.pima.gov/ | |
| 01/21/2025 | SPECIAL INSPECTION FOR SITE PREPARATION IS REQUIRED. | |
| 01/21/2025 | Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building. |
Outstanding Inspections
Permit Status: Issued
Permit Number: T22CM01074
Permite Description: SFR MPLAN1510 T20-M0040
Total Outstanding Inspections - 6
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/24/2025 | COT - RSEL - Grounding/Bonding | N/A | Partial Pass | 2-24-25, partial pass for ufer only. |
| 03/28/2025 | COT - RSBU - Interior Shear Bracing | N/A | Not Applicable | house fully wrapped in plywood, not using interior shear |
| 03/28/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | N/A | Partial Pass | Passed 3/28/24 ok to drywall |
| 05/12/2025 | RSEL - Electrical Progress | N/A | Re-inspection required | 5-12-25, block 4-gang box, firefoam all penetrations at top plates, DWV not under test, electrical receptacles/light switches not made up at missing stairs, electrical schedule does not match # of circuits-provide an updated schedule to the city for review/approval or add circuits according to approved plans. Exhaust's are not permitted to be located underneath soffits and prohibited from discharging onto a sidewalk, walking surface as it may cause moisture and a slippery surface. Duct termination shall terminate not less than 3' from in any direction from openings into buildings. Exhaust duct termination shall be equipped with a backdraft damper. See M1501.1, M1502.3 & M1502.3.2 for details. Also, add a CS16 strap to top plates where over notched more than 40% on interior non bearing framing. |
| 05/12/2025 | RSME - Mechanical Progress | N/A | Partial Pass | |
| 05/21/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | N/A | Partial Pass | 5/21/25 1. Partial pass; Okay to proceed with drywall on firewalls. |
Completed Inspections
Permit Status: Issued
Permit Number: T22CM01074
Permit Description: SFR MPLAN1510 T20-M0040
Total Completed Inspections - 17
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2025 | COT - RSPL - Rough Soil | Passed | Passed 1/22/25 ok to backfill | |
| 01/22/2025 | COT - RSPL - Sewer | Passed | Passed 1/22/25 ok to backfill | |
| 02/07/2025 | COT - RSBU - Excavation/Rebar/Zoning | Passed | 2/7/25 pass | |
| 02/07/2025 | COT - RSBU - Preslab | Passed | 2/7/25 pass | |
| 03/28/2025 | BULD - Electrical Clearance | Passed | Passed 3/28/25 ready for temp power clearance eco | |
| 03/28/2025 | COT - RSBU - Roof Nailing | Passed | Roof nailing and truss per plan | |
| 04/07/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | ||
| 04/29/2025 | COT - RSPL - Yard Water Line | Passed | Main water line for lot #8, partial main line for lot #7. OK to cover progress areas. | |
| 05/12/2025 | COT - RSPL - Gas Pressure Test | Passed | 5-12-25, approved. | |
| 05/12/2025 | RSPL - Plumbing Progress | Passed | 5-12-25, block 4-gang box, firefoam all penetrations at top plates, DWV not under test, electrical receptacles/light switches not made up at missing stairs, electrical schedule does not match # of circuits-provide an updated schedule to the city for review/approval or add circuits according to approved plans. Exhaust's are not permitted to be located underneath soffits and prohibited from discharging onto a sidewalk, walking surface as it may cause moisture and a slippery surface. Duct termination shall terminate not less than 3' from in any direction from openings into buildings. Exhaust duct termination shall be equipped with a backdraft damper. See M1501.1, M1502.3 & M1502.3.2 for details. Also, add a CS16 strap to top plates where over notched more than 40% on interior non bearing framing. Condenser unit not installed. | |
| 06/10/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | 6/10/2025 all corrections have been made. Okay to insulate and drywall. | |
| 06/18/2025 | COT - RSBU - Firewall/Fire Barrier/Firestop | Passed | 6/18/25 Pass |
|
| 12/03/2025 | COT - RSEL - Electrical Final | Passed | ||
| 12/03/2025 | COT - RSPL - Plumbing Final | Passed | ||
| 12/03/2025 | RSBU - Building Final | Passed | ||
| 12/03/2025 | COT - RSME - Mechanical Final | Passed | ||
| 12/03/2025 | COT - RSEL - Outdoor Lighting | Passed |