Permit: T22CM01074

Parcel: 116214580

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Permit Number - T22CM01074

Inspection Description - COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
05/12/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required 5-12-25, block 4-gang box, firefoam all penetrations at top plates, DWV not under test, electrical receptacles/light switches not made up at missing stairs, electrical schedule does not match # of circuits-provide an updated schedule to the city for review/approval or add circuits according to approved plans. Exhaust's are not permitted to be located underneath soffits and prohibited from discharging onto a sidewalk, walking surface as it may cause moisture and a slippery surface. Duct termination shall terminate not less than 3' from in any direction from openings into buildings. Exhaust duct termination shall be equipped with a backdraft damper. See M1501.1, M1502.3 & M1502.3.2 for details. Also, add a CS16 strap to top plates where over notched more than 40% on interior non bearing framing.
05/14/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required 5-12-25, block 4-gang box, firefoam all penetrations at top plates, DWV not under test, electrical receptacles/light switches not made up at missing stairs, electrical schedule does not match # of circuits-provide an updated schedule to the city for review/approval or add circuits according to approved plans. Exhaust's are not permitted to be located underneath soffits and prohibited from discharging onto a sidewalk, walking surface as it may cause moisture and a slippery surface. Duct termination shall terminate not less than 3' from in any direction from openings into buildings. Exhaust duct termination shall be equipped with a backdraft damper. See M1501.1, M1502.3 & M1502.3.2 for details. Also, add a CS16 strap to top plates where over notched more than 40% on interior non bearing framing.
5/14/25: NOT READY FOR INSPECTION, LATH MUST BE COMPLETE BEFORE CALLING FOR INTERMEDIATE INSPECTION. IPC T308.5 DWV must be supported midway on vertical runs, IPC T308.5 DWV must be supported every 4' on horizontal runs, IRC R302.11 blocking/ draft stop required at drop ceiling at main floor, IRC R302.11 all penetrations must be sealed through top plates and vapor barrier, IFGC G2424.1 support gas piping at range in wall, up stairs double lav must be properly pitched, DWV not fully under test, Vent at main floor bathroom cannot terminate in between floors, nail plates missing throughout, proper nail plates required at plumbing walls. STOPPED INSPECTION MORE ITEMS MAY BE ADDED.
05/15/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required 5-12-25, block 4-gang box, firefoam all penetrations at top plates, DWV not under test, electrical receptacles/light switches not made up at missing stairs, electrical schedule does not match # of circuits-provide an updated schedule to the city for review/approval or add circuits according to approved plans. Exhaust's are not permitted to be located underneath soffits and prohibited from discharging onto a sidewalk, walking surface as it may cause moisture and a slippery surface. Duct termination shall terminate not less than 3' from in any direction from openings into buildings. Exhaust duct termination shall be equipped with a backdraft damper. See M1501.1, M1502.3 & M1502.3.2 for details. Also, add a CS16 strap to top plates where over notched more than 40% on interior non bearing framing.
5/15/25: verified DWV and Domestic under test, Nail plates required required throughout and shall be 4"x8" at plumbing walls for top plate and sole plates, Horizontal runs for DVW require support 4' o.c, all penetrations must be sealed through top plate at exterior and interior walls including all walls that have a drop ceiling, Gas piping must be appropriately supported at horizontal run in garage.
05/21/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Partial Pass 5/21/25
1. Partial pass; Okay to proceed with drywall on firewalls.
06/06/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required 6/6/2025 stack vent at laundry has to be minimum 18". Add fire blocking to all soffit areas.
06/10/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed 6/10/2025 all corrections have been made. Okay to insulate and drywall.