Permit: T21FC00507
Permit Details
Apply Date:
06/22/2021
Applicant:
Description:
Automatic Fire Extingshing Sys - Installation of a Wet pipe sprinkler system mezzanine and 2nd floor
Outstanding Inspections
Permit Status: Expired
Permit Number: T21FC00507
Permite Description: Automatic Fire Extingshing Sys - Installation of a Wet pipe sprinkler system mezzanine and 2nd floor
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/07/2022 | COT - FCON - Sprinkler - Final | N/A | Canceled | Inspection Canceled |
Completed Inspections
Permit Status: Expired
Permit Number: T21FC00507
Permit Description: Automatic Fire Extingshing Sys - Installation of a Wet pipe sprinkler system mezzanine and 2nd floor
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/23/2021 | FCON – OH Piping & Hydro | Passed | {Activity date: 11/23/2021; Status: Approved; Inspector: wmotto1; Comment: Entered by WMOTTO1 - 1. The overhead 200lb test approved via face time. Need to verify placement at final. This is for the 2nd floor. 2 inch drain test 65-65-65 water flow set alarm off in 45 seconds} ; {Activity date: 11/03/2021; Status: Partial Approval; Inspector: wmotto; Comment: Entered by WMOTTO1 - 200 pound test first floor approved. Ok to cover pipe on the first floor} |