Permit: T21FC00507

Parcel: 117200270


Addresses:

260 S CHURCH AV

Inspection Status: Passed

Inspection History: FCON – OH Piping & Hydro

Date Description Inspector Results Comments
11/23/2021 FCON – OH Piping & Hydro wmotto1 Approved Entered by WMOTTO1 - 1. The overhead 200lb test approved via face time. Need to verify placement at final. This is for the 2nd floor. 2 inch drain test 65-65-65 water flow set alarm off in 45 seconds
11/03/2021 FCON – OH Piping & Hydro wmotto Partial Approval Entered by WMOTTO1 - 200 pound test first floor approved. Ok to cover pipe on the first floor