Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Complete
Type:
Commercial Building
Address:
7139 E 22ND ST
Apply Date:
11/01/2021
Applicant:
Description:
Tenant Improvement to existing building C of O issued

Permit Reviews

Permit Number - T21CM08602
Permit Status: Complete
Permit Description: Tenant Improvement to existing building C of O issued
Start Date Submittal Complete Date Status  
01/31/2022 RESUBMITTAL 02/02/2022 COMPLETED Review Details
02/04/2022 RESUBMITTAL 02/05/2022 COMPLETED Review Details
11/01/2021 COMMERCIAL - BLDG/FIRE/ZONING/ENG 11/23/2021 COMPLETED Review Details
12/02/2021 RESUBMITTAL 12/16/2021 COMPLETED Review Details
12/20/2021 RESUBMITTAL 01/10/2022 COMPLETED Review Details
12/12/2022 BUILDING DEFERRED SUBMITTAL REVIEW v.1 N/A IN REVIEW Review Details

Outstanding Activity Conditions

Permit Number - T21CM08602
Permit Status: Complete
Permit Description: Tenant Improvement to existing building C of O issued
Total Outstanding Activity Conditions - 3
Date Name
12/27/2021 SPECIAL INSPECTION FOR STRUCTURAL WELDING IS REQUIRED.
12/27/2021 SPECIAL INSPECTION FOR STRUCTURAL MASONRY IS REQUIRED.
12/27/2021 SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED.

Outstanding Inspections

Permit Status: Complete
Permit Number: T21CM08602
Permite Description: Tenant Improvement to existing building C of O issued
Total Outstanding Inspections - 7
Last Inspection Date Description Inspector Results Comments
10/26/2022 COT - LCEL - Outdoor Lighting N/A Not Ready
10/26/2022 COT - LCBU - Sustainability N/A Not Ready
10/27/2022 COT - LCBU - Framing N/A Not Ready
10/26/2022 COT - LCEL - Electrical Underground N/A Not Ready
10/26/2022 COT - LCPL - Backwater Valve N/A Not Ready
12/01/2022 COT - LCME - Mechanical Final N/A Partial Pass pending balance report..
12/01/2022 ENGR Engineering Final N/A Complete (Recurring) Contractor needs to complete handicap parking the railing entering the building on the west side of

Completed Inspections

Permit Status: Complete
Permit Number: T21CM08602
Permit Description: Tenant Improvement to existing building C of O issued
Total Completed Inspections - 23
Date Description Inspector Results Comments
08/01/2022 COT - LCBU - Preslab Passed {Activity date: 08/01/2022; Status: Approved; Inspector: RCHANDLER; Comment: Entered by VVERA1 - Approved. Corrections completed.} ; {Activity date: 07/28/2022; Status: Not ready for Inspection; Inspector: TLUNDBERG; Comment: Entered by NGARCIA3 - NR
All entrances boarded up, no access} ; {Activity date: 07/27/2022; Status: Not ready for Inspection; Inspector: TLUNDBERG; Comment: Entered by VVERA1 - NR
New soil line not under test.}
08/30/2022 COT - LCEL - Electrical Intermediate Passed {Activity date: 08/30/2022; Status: Approved; Inspector: JBURGE; Comment: Entered by NGARCIA3 - Approved. Ok to cover walls.} ; {Activity date: 07/18/2022; Status: Partial Approval; Inspector: RCHANDLER; Comment: Entered by VVERA1 - pA. Walls.} ; {Activity date: 07/18/2022; Status: Cancelled; Inspector: IVR USER; Comment: Entered by IVR USER - IVRS - RI canceled} ; {Activity date: 07/11/2022; Status: Not ready for Inspection; Inspector: WGALLAGHER; Comment: Entered by VVERA1 - Not ready
}
08/30/2022 COT - LCPL - Plumbing Intermediate Passed {Activity date: 08/30/2022; Status: Approved; Inspector: JBURGE; Comment: Entered by NGARCIA3 - Approved. Ok to cover walls.}
08/30/2022 COT - LCME - Mechanical Intermediate Passed {Activity date: 08/30/2022; Status: Approved; Inspector: JBURGE; Comment: Entered by NGARCIA3 - Approved. Ok to cover walls.}
08/30/2022 COT - HCBU - Interior Shear Bracing Passed {Activity date: 08/30/2022; Status: Approved; Inspector: JBURGE; Comment: Entered by NGARCIA3 - Approved. Ok to tape throughout.
}
09/22/2022 COT - LCBU - Building Above Ceiling Passed {Activity date: 09/22/2022; Status: Approved; Inspector: RCHANDLER; Comment: Entered by NGARCIA3 - AP}
09/22/2022 COT - LCEL - Electrical Progress Passed {Activity date: 09/22/2022; Status: Approved; Inspector: RCHANDLER; Comment: Entered by NGARCIA3 - AP}
09/22/2022 COT - LCPL - Plumbing Progress Passed {Activity date: 09/22/2022; Status: Approved; Inspector: RCHANDLER; Comment: Entered by NGARCIA3 - AP}
09/22/2022 COT - LCME - Mechanical Above Ceiling Passed {Activity date: 09/22/2022; Status: Approved; Inspector: RCHANDLER; Comment: Entered by NGARCIA3 - AP}
09/22/2022 COT - LCME - Mechanical Progress Passed {Activity date: 09/22/2022; Status: Approved; Inspector: RCHANDLER; Comment: Entered by NGARCIA3 - AP}
09/22/2022 COT - LCPL - Plumbing Above Ceiling Passed {Activity date: 09/22/2022; Status: Approved; Inspector: RCHANDLER; Comment: Entered by NGARCIA3 - AP}
09/22/2022 COT - LCEL - Electrical Above Ceiling Passed {Activity date: 09/22/2022; Status: Approved; Inspector: RCHANDLER; Comment: Entered by NGARCIA3 - AP}
09/22/2022 COT - LCBU - Building Progress Passed {Activity date: 09/22/2022; Status: Approved; Inspector: RCHANDLER; Comment: Entered by NGARCIA3 - AP}
10/05/2022 PDSD Building Division - TEP PM Clearance Passed {Activity date: 10/05/2022; Status: Approved; Inspector: DQUINN; Comment: Entered by VVERA1 - CODE INCR}
10/05/2022 COT - LCEL - Service Upgrade Passed {Activity date: 10/05/2022; Status: Approved; Inspector: DQUINN; Comment: Entered by VVERA1 - Ap

Clear incr}
10/26/2022 COT - FCON - Alarm - Final Passed
10/26/2022 COT - FCON - Fire - Final Passed Need to fix sprinkler coverage in drive through area and the riser room. Need to change heads to the proper type of heads for the drive through area. Need to fix the inpector test valve so that a proper inspection can be done. Need a current five year and annual inspection on the sprinkler system showing zero deficiencies. Need to monitor the tamper/post indicating valve. Need FACP sign and riser room sign on door leading to the riser and alarm room.
12/01/2022 COT - LCPL - Plumbing Final Passed
12/01/2022 COT - LCEL - Electrical Final Passed
12/01/2022 COT - LCBU - Building Final Passed
12/07/2022 COT - FCON - Sprinkler - Final Passed
12/08/2022 SITE - Zoning Final Passed
12/08/2022 ENGR Engineering Final Passed N/A

Documents

File Name Document Type  
COFO_FINALCOFO_COMMERCIAL.PDF DOCUMENTS VIEW
APPLICATION.PDF DOCUMENTS VIEW
JOB CARD.PDF DOCUMENTS VIEW
CONTRACTOR LETTER.PDF DOCUMENTS VIEW
PERMIT.PDF DOCUMENTS VIEW
SPECIAL INSPECTION CERT.PDF DOCUMENTS VIEW
STRUCTURAL CALCS.PDF DOCUMENTS VIEW
PLAN SET.PDF CONSTRPLANS VIEW
LICENSE CERTIFICATE.PDF DOCUMENTS VIEW