Inspection Status: Passed
Inspection History: COT - FCON - Fire - Final
| Date |
Description |
Inspector |
Results |
Comments |
| 10/26/2022 |
COT - FCON - Fire - Final |
|
Passed |
Need to fix sprinkler coverage in drive through area and the riser room. Need to change heads to the proper type of heads for the drive through area. Need to fix the inpector test valve so that a proper inspection can be done. Need a current five year and annual inspection on the sprinkler system showing zero deficiencies. Need to monitor the tamper/post indicating valve. Need FACP sign and riser room sign on door leading to the riser and alarm room. |
| 11/03/2021 |
COT - FCON - Fire - Final |
jvincent |
Prior to Final Inspectn |
Entered by JVINCEN1 - -Verify all door hardware/card access, etc... is installed prior to final. |