Permit Number: T21CM08602
Parcel: Unknown

Address:
7139 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM08602
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2021 JVINCEN1 FIRE REVIEW Approved
11/18/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM08602

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. Provide an existing/demolition plan.
2. The construction type is listed as type III construction. Indicate whether it is type IIIA or IIIB construction and coordinate and applicable requirements.
3. The occupant load for the fulfillment area is calculated incorrectly. This is similar to a business area and should be calculated at 150 per sq. ft. The MED VIP room is not included in the calculation. Provide a table of each space along with the calculation for each space.

MECHANICAL REVIEW COMMENTS:
Denied
1. Provide an approved mechanical ventilation system with CO and NO2 detectors in the enclosed parking garage (intake room) (IMC2018,404)

ELECTRICAL REVIEW COMMENTS
Denied
E1.0: No electrical issues
E2.0: No electrical issues.
FYI: Provided IEC 2018 energy calculations which meet comcheck requirement for this reviewer. Other reviewers may
require output from comcheck software (free to download and use) on future submittals.
E2.1: No electrical issues
E3.0: No electrical issues
E4.0: Fire alarm plan needs to show pull stations at all normal and emergency egress points.
E5.0: Tucson requires fault current calculations to new panels.
E5.0: Rooftop units HP2, 3, 4, & 5 are under reported on panel schedule L1 vs AMPS shown on E3.0 Mechanical Equipment Schedule. Does not affect design.

PLUMBING REVIEW COMMENTS:
Denied
1). Condensate discharge to the sanitary needs to be indirect. update general note #6 on Plan pg. P1.0. -IPC 802.1.5
2). Can't replace the High/Low drinking fountain with a bottle filler only. A High/low drinking fountain will need to be reinstalled with or without a bottle filler attachment. Update P6 on fixture schedule on plan pg. P2.0 & Keynote #6 on P1.0 -IPC 410.3 410.4
11/22/2021 SSHIELD1 ENGINEERING REVIEW Passed
11/22/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/22/2021 ROBERT SHERRY WATER REVIEW Completed
11/22/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM08602
7139 E 22nd St – C-2
Marijuana Dispensary w/Drive-through

TRANSMITTAL: November 22, 2021
This site is located in the C-2 zone (UDC 4.7.21). Marijuana Dispensary use is allowed in the zone (Table 4.8-4) subject to Use Specific Standard 4.9.9.E.1.

1. The proposed dispensary exceeds the allowed 10,000 square footage per UDC Article 4.9.9.E.1.a.

2. Provide a calculation that clearly demonstrates that the requirement of UDC Article 4.9.9.E.1.d is met.

3. Clearly demonstrate on the plans how the requirements of UDC Article 4.9.9.E.1.I are met.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/23/2021 NGARCIA3 OUT TO CUSTOMER Completed