Permit: T21CM07224
Permit Details
Status:
Inspections Complete
Type:
Residential Building - One or Two Family
Address:
5409 S ALASKA DR
Address NEW:
5409 S ALASKA DR
Apply Date:
09/08/2021
Applicant:
Juan Puerto
Description:
Renovate Storage Building to Dwelling Unit
Permit Reviews
Permit Number - T21CM07224
Permit Status: Inspections complete
Permit Description: Renovate Storage Building to Dwelling Unit
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 09/08/2021 | RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO | 10/05/2021 | COMPLETED |
| 11/02/2021 | RESUBMITTAL | 11/09/2021 | COMPLETED |
| 12/03/2021 | RESUBMITTAL | 12/14/2021 | COMPLETED |
Outstanding Inspections
Permit Status: Inspections Complete
Permit Number: T21CM07224
Permite Description: Renovate Storage Building to Dwelling Unit
Total Outstanding Inspections - 9
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2022 | COT - RSEL - Grounding/Bonding | N/A | Canceled | {Activity date: 03/22/2022; Status: Not Applicable; Inspector: DMUNIZ; Comment: Entered by VVERA1 - not applicable} |
| 11/04/2022 | COT - RSPL - Yard Water Line | N/A | Canceled | Inspection Canceled |
| 11/04/2022 | COT - RSEL - Construction Power | N/A | Canceled | Inspection Canceled |
| 11/04/2022 | COT - RSEL - Service Upgrade | N/A | Canceled | Inspection Canceled |
| 10/11/2023 | BULD - Electrical Clearance | N/A | Re-inspection required | Texted at 7:06am. Called at 2:07pm. No answer. |
| 11/07/2022 | COT - RSPL - Gas Pressure Test | N/A | Canceled | Inspection Canceled |
| 05/29/2024 | COT - RSEL - Electrical Final | N/A | Re-inspection required | 5/29/24: mini splits are being over Amped, disconnect boxes required at mini splits, properly terminate condensate lines 6" above grade, sediment trap required at water heater, tape must be removed at water heater vent, exterior receptacles must be WR, smoke alarms must be interconnected, water hammer arrestors missing at laundry, GFCI request disposal, clean out cap required at exterior, anti-tip at range missing, seal all penetrations going through vapor barrier, arc-fault breaker's missing throughout, panel schedule must be area specific. STOPPED INSPECTION MORE ITEMS MAY BE ADDED. |
| 05/29/2024 | COT - RSME - Mechanical Final | N/A | Re-inspection required | 5/29/24: mini splits are being over Amped, disconnect boxes required at mini splits, properly terminate condensate lines 6" above grade, sediment trap required at water heater, tape must be removed at water heater vent, exterior receptacles must be WR, smoke alarms must be interconnected, water hammer arrestors missing at laundry, GFCI request disposal, clean out cap required at exterior, anti-tip at range missing, seal all penetrations going through vapor barrier, arc-fault breaker's missing throughout, panel schedule must be area specific. STOPPED INSPECTION MORE ITEMS MAY BE ADDED. |
| 05/29/2024 | COT - RSPL - Plumbing Final | N/A | Re-inspection required | 5/29/24: mini splits are being over Amped, disconnect boxes required at mini splits, properly terminate condensate lines 6" above grade, sediment trap required at water heater, tape must be removed at water heater vent, exterior receptacles must be WR, smoke alarms must be interconnected, water hammer arrestors missing at laundry, GFCI request disposal, clean out cap required at exterior, anti-tip at range missing, seal all penetrations going through vapor barrier, arc-fault breaker's missing throughout, panel schedule must be area specific. STOPPED INSPECTION MORE ITEMS MAY BE ADDED. |
Completed Inspections
Permit Status: Inspections Complete
Permit Number: T21CM07224
Permit Description: Renovate Storage Building to Dwelling Unit
Total Completed Inspections - 16
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2022 | COT - RSPL - Rough Soil | Passed | {Activity date: 02/15/2022; Status: Approved; Inspector: TGAUSP; Comment: Entered by VVERA1 - Approved, okay to backfill progress areas} | |
| 02/15/2022 | COT - RSBU - Excavation/Rebar/Zoning | Passed | {Activity date: 02/15/2022; Status: Approved; Inspector: TGAUSP; Comment: Entered by VVERA1 - Approved addition mono-pour} | |
| 03/08/2022 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | {Activity date: 03/08/2022; Status: Approved; Inspector: TGAUSP; Comment: Entered by VVERA1 - Approved} | |
| 03/08/2022 | COT - LCBU - Framing | Passed | {Activity date: 03/08/2022; Status: Approved; Inspector: TGAUSP; Comment: Entered by VVERA1 - Approved} | |
| 03/08/2022 | COT - LCPL - Plumbing Intermediate | Passed | {Activity date: 03/08/2022; Status: Approved; Inspector: TGAUSP; Comment: Entered by VVERA1 - Approved} ; {Activity date: 02/15/2022; Status: Not ready for Inspection; Inspector: TGAUSP; Comment: Entered by VVERA1 - NR} | |
| 03/08/2022 | RSME - Mechanical Progress | Passed | {Activity date: 03/08/2022; Status: Approved; Inspector: TGAUSP; Comment: Entered by VVERA1 - Approved, mini-splits} | |
| 03/22/2022 | COT - RSBU - Roof Nailing | Passed | {Activity date: 03/22/2022; Status: Approved; Inspector: DMUNIZ; Comment: Entered by VVERA1 - Approved} ; {Activity date: 03/09/2022; Status: Correction Required; Inspector: DMUNIZ; Comment: Entered by RSALDAT1 - corrections required, nail decking where missed, provide ladder for further inspection.} | |
| 03/22/2022 | COT - RSBU - Preslab | Passed | {Activity date: 03/22/2022; Status: Approved; Inspector: DMUNIZ; Comment: Entered by VVERA1 - Approved} | |
| 03/22/2022 | COT - RSEL - Electrical Underground | Passed | {Activity date: 03/22/2022; Status: Approved; Inspector: DMUNIZ; Comment: Entered by VVERA1 - Approved} | |
| 03/22/2022 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | {Activity date: 03/22/2022; Status: Approved; Inspector: DMUNIZ; Comment: Entered by VVERA1 - Approved} ; {Activity date: 03/09/2022; Status: Correction Required; Inspector: DMUNIZ; Comment: Entered by RSALDAT1 - corrections required, nail sheathing where missed and nail all clips where missing nails. Install missing anchor bolts at sill plate.} ; {Activity date: 03/08/2022; Status: Partial Approval; Inspector: TGAUSP; Comment: Entered by RSALDAT1 - INSPECTOR DM CHANGED AP TO PA. SEE NEXT ENTRY.} | |
| 12/18/2023 | BULD - Electrical Clearance | Passed | 12/18/23 ECO unit B | |
| 12/18/2023 | COT - RSPL - Gas Pressure Test | Passed | ||
| 12/13/2024 | RSBU - Building Final | Passed | ||
| 12/13/2024 | COT - RSEL - Electrical Final | Passed | ||
| 12/13/2024 | COT - RSME - Mechanical Final | Passed | ||
| 12/13/2024 | COT - RSPL - Plumbing Final | Passed |