Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
Commercial Building
Address:
6161 S PARK AV
Address NEW:
6161 S PARK AV
Apply Date:
06/25/2020
Applicant:
Description:
ADD UPGRADED ELECTRICAL SERVICE PANEL

Permit Reviews

Permit Number - T20CM04004
Permit Status: Expired
Permit Description: ADD UPGRADED ELECTRICAL SERVICE PANEL
Start Date Submittal Complete Date Status  
02/02/2021 RESUBMITTAL 02/11/2021 COMPLETED Review Details
06/25/2020 OTHER 07/27/2020 COMPLETED Review Details
07/27/2020 RESUBMITTAL 08/05/2020 COMPLETED Review Details
08/28/2020 REVISION - - 1ST 02/02/2021 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T20CM04004
Permit Status: Expired
Permit Description: ADD UPGRADED ELECTRICAL SERVICE PANEL
Total Outstanding Activity Conditions - 1
Date Name
06/25/2020 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T20CM04004
Permite Description: ADD UPGRADED ELECTRICAL SERVICE PANEL
Total Outstanding Inspections - 6
Last Inspection Date Description Inspector Results Comments
11/04/2022 COT - LCEL - Construction Power N/A Canceled Inspection Canceled
11/04/2022 COT - LCEL - Temporary Service N/A Canceled Inspection Canceled
11/07/2022 COT - LCEL - Electrical Intermediate N/A Canceled Inspection Canceled
11/07/2022 COT - LCEL - Electrical Underground N/A Canceled Inspection Canceled
11/07/2022 COT - LCEL - Electrical Final N/A Canceled Inspection Canceled
11/07/2022 COT - LCEL - Grounding/Bonding N/A Canceled Inspection Canceled

Completed Inspections

Permit Status: Expired
Permit Number: T20CM04004
Permit Description: ADD UPGRADED ELECTRICAL SERVICE PANEL
Total Completed Inspections - 2
Date Description Inspector Results Comments
12/22/2020 BULD - Electrical Clearance Passed {Activity date: 12/22/2020; Status: Approved; Inspector: DMUNIZ; Comment: Entered by RSALDAT1 - CODE INCR/SE CT}
12/22/2020 COT - LCEL - Service Upgrade Passed {Activity date: 12/22/2020; Status: Approved; Inspector: DMUNIZ; Comment: Entered by RSALDAT1 - Approved, Clear TEP INCR Ok to energize new Service entrance CT.} ; {Activity date: 12/07/2020; Status: Not ready for Inspection; Inspector: WGALLAGHER; Comment: Entered by PAHUMAD1 - Not Ready, need verification that CT can is TEP approved. Re identify current carrying conductor on service entrance. Service is 120/240V single phase system.(Remove Orange, & Identify Red). Re direct weather heads towards drop location, Install permanent address label and identify each individual Disconnect. Install ground throughout system and terminate conductors in CT/Disconnect/Gutter to disconnects.}

Documents

File Name Document Type  
JAIME EELECTRIC LLC WORK AUTHORIZATION 2024 MASS-UPLOAD.PDF DOCUMENTS VIEW
JOB CARD 2024 MASS-UPLOAD.PDF DOCUMENTS VIEW
PERMIT 2024 MASS-UPLOAD.PDF DOCUMENTS VIEW
PLAN SET 2024 MASS-UPLOAD.PDF DOCUMENTS VIEW
JAIME EELECTRIC LLC WORK AUTHORIZATION.PDF DOCUMENTS VIEW
JOB CARD.PDF DOCUMENTS VIEW
PERMIT.PDF DOCUMENTS VIEW
PLAN SET.PDF DOCUMENTS VIEW
1_PLAN_SET.PDF CONSTRPLANS VIEW
1_APPLICATION.PDF DOCUMENTS VIEW
1595513634139_PM E2.0 .PDF DOCUMENTS VIEW
PERMIT.PDF DOCUMENTS VIEW
PM ES1.0 .PDF DOCUMENTS VIEW
PM E0.1 .PDF CONSTRPLANS VIEW