Inspection Status: Canceled
Inspection History: COT - LCEL - Electrical Underground
| Date |
Description |
Inspector |
Results |
Comments |
| 11/07/2022 |
COT - LCEL - Electrical Underground |
|
Canceled |
Inspection Canceled |
| 02/22/2021 |
COT - LCEL - Electrical Underground |
TGAUSP |
Partial Approval |
Entered by BSTEVENS - Approved for Units 1, 28, 33-38 and 64 (total of 9 MH’s), okay to backfill
|
| 02/05/2021 |
COT - LCEL - Electrical Underground |
BSTEVENS |
Partial Approval |
Entered by BSTEVENS - UNITS 63 TO 46 OK TO COVER CONDUCTORS |
| 01/29/2021 |
COT - LCEL - Electrical Underground |
RBOOHER |
Partial Approval |
Entered by VLEON1 - Partial...Not per plan. Revision not approved.. Cover at own risk, provide pictures with sufficient detail showing direct burial on cables, trench depth., everything to match new plans if approved... |
| 01/20/2021 |
COT - LCEL - Electrical Underground |
RBOOHER |
Denied |
Entered by VLEON1 - DENIED - Denied... Engineer specified in plans to use conduit , no conduit used at time of inspection.. verified wire sizing and burial depth. Will need a change order from engineer approving change..
|