Inspection History Details
Inspection Status: Canceled
Inspection History: COT - LCEL - Electrical Underground
Permit Number - T20CM04004
Inspection Description - COT - LCEL - Electrical Underground
Inspection Status - Canceled
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/07/2022 | COT - LCEL - Electrical Underground | Canceled | Inspection Canceled | |
| 02/22/2021 | COT - LCEL - Electrical Underground | TGAUSP | Partial Approval | Entered by BSTEVENS - Approved for Units 1, 28, 33-38 and 64 (total of 9 MH’s), okay to backfill |
| 02/05/2021 | COT - LCEL - Electrical Underground | BSTEVENS | Partial Approval | Entered by BSTEVENS - UNITS 63 TO 46 OK TO COVER CONDUCTORS |
| 01/29/2021 | COT - LCEL - Electrical Underground | RBOOHER | Partial Approval | Entered by VLEON1 - Partial...Not per plan. Revision not approved.. Cover at own risk, provide pictures with sufficient detail showing direct burial on cables, trench depth., everything to match new plans if approved... |
| 01/20/2021 | COT - LCEL - Electrical Underground | RBOOHER | Denied | Entered by VLEON1 - DENIED - Denied... Engineer specified in plans to use conduit , no conduit used at time of inspection.. verified wire sizing and burial depth. Will need a change order from engineer approving change.. |