Inspection Status: Passed
Inspection History: COT - LCEL - Service UpgradeĀ
| Date |
Description |
Inspector |
Results |
Comments |
| 12/22/2020 |
COT - LCEL - Service UpgradeĀ |
DMUNIZ |
Approved |
Entered by RSALDAT1 - Approved, Clear TEP INCR Ok to energize new Service entrance CT. |
| 12/07/2020 |
COT - LCEL - Service UpgradeĀ |
WGALLAGHER |
Not ready for Inspection |
Entered by PAHUMAD1 - Not Ready, need verification that CT can is TEP approved. Re identify current carrying conductor on service entrance. Service is 120/240V single phase system.(Remove Orange, & Identify Red). Re direct weather heads towards drop location, Install permanent address label and identify each individual Disconnect. Install ground throughout system and terminate conductors in CT/Disconnect/Gutter to disconnects. |