Permit: T19CM02812
Permit Details
Apply Date:
04/18/2019
Applicant:
ELPIDIO MEDRANO
Description:
ELECTRICAL RECONNECT
Outstanding Activity Conditions
Permit Number - T19CM02812
Permit Status: Final
Permit Description: ELECTRICAL RECONNECT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 04/18/2019 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T19CM02812
Permit Description: ELECTRICAL RECONNECT
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/02/2019 | ELECTRIC - RECONNECT | GWEST | Approved | NEEDS TO SCHEDULE 2065, 2070 IS NOT NEEDED. SEE INSPECTOR NOTES BELOW-CB Go to COT and upgrade permit to a Service Panel Upgrade, this is a new panel and not a Reconnect. Contact TEP for a panel spot or approve the panel location you have chosen. This is a new 200 amp Panel and requires the following: 2 8’ ground rods a min of 6’ apart. A #4 GEC water and gas bond. 2 brackets to support the service mast above the panel at the wall. 2/0 copper or 4/0 aluminum service entrance cables. IRC 3603.1. Remove paint from gas pipe for a pure bond to that pipe with the gas bond clamp #12 ga wire for 20 amp and #14 for 15 amp circuits. Label all breaker functions in the panel. Drive ground rods flush or below grade so rods are in contact with earth for 8 feet. |
| 05/06/2019 | TEP CLEARANCE - PM | DQUINN | Approved | CODE INCR |
| 05/06/2019 | ELECTRIC - FINAL | DQUINN | Approved | |
| 05/06/2019 | ELECTRIC - SERVICE UPGRADE | DQUINN | Approved | Clear incr |